Troubleshooting

Pumping system troubleshooting

Symptom

Cause

Remedy

There is no circulation

Air-bound system

Vent the system

The impeller or piping is clogged.

Locate and remove the obstruction.

The system valve is closed.

Open

The electrical circuit for the pump is

broken.

Check all related low and line voltage

circuits.

There is inadequate circulation.

Air-bound system

Vent the system.

The impeller or piping is clogged.

Locate and remove the obstruction.

The impeller is damaged.

Replace pump.

The pump is too small.

Replace the pump if single speed. If

three speed switch to higher setting.

Partially air-bound pump

Vent the pump casing.

Improper motor speed

Check the wiring and the voltage.

There is pump or system noise.

Entrained air

Vent the system.

Pump cavitation

Lower the pump or raise pressure or

relocate (see note below).

Excessive water velocity

Install balancing cocks or parallel

piping.

Pipe vibration

Provide adequate pipe support.

There is premature failure of pump

components.

Improper pump (size/type)

Replace

Improper pump location

Relocate

Excessive water treatment

Check the manufacturer’s

instructions.

Pump operating close to or beyond

the end point of curve.

Balance the system.

Excessive piping load

Provide proper pipe support

There are seal failures within a 1–year

period or less in a closed system.

Excessive dirt, sand and oxides

Clean the system.

Excessive or improper water

treatment

Check for proper water treatment

recommendations from pump

manufacturer.

Pump Cavitation:
1. Improper selection
2. Compression tank location

1. Check pump operation on its

curve — overloading

2. High head pump must have

compression tank on suction

side of pump.

Excessive temperatures

Check the type of seal and maximum

operating temperature from the

manufacturer.

Pumps run without fluid

Pumps must be primed before

operation.

There is seal pitting, oxygen

corrosion, magnetic iron oxide.

Caused by wear and excessive

amounts of free oxygen.

Check if system has a constant leak.

Fresh water feeding carries oxygen

into the system.

Troubleshooting