Bell & Gossett P86315B ZoneTrol II AZ-1A User Manual

Zonetrol ii, Model az-1a, Instruction manual

Advertising
background image

SAFETY
INSTRUCTIONS

This safety alert symbol will be used in this manual and on the pump

safety instructions decal to draw attention to safety related instruc-

tions. When used, the safety alert symbol means ATTENTION!

BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOL-

LOW THE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.

DESCRIPTION

The AZ-1A pump controller is field mounted to any NRF, NBF, SSF or

1

/

12

-

1

/

6

HP Series PL

TM

booster pump. The AZ-1A controller operates

the pump when the thermostat calls for heat. The controller can be

wired to fire the boiler through a 24-volt rated isolated endswitch. The

AZ-1A pump controllers are UL and cUL listed. When the AZ-1A is

mounted on a B&G pump, the pump/controller assembly maintains

the UL listings.

OPERATIONAL LIMITS

For use on B&G models NRF, NBF, SSF, and

1

/

12

-

1

/

6

HP Series PL

TM

only.

Do not use with pump that has larger than

1

/

6

HP motor.

Power Supply: 115-120 VAC, 60HZ, 1Ø
Maximum switch current: 5 Amps

OPERATION

The circulators wired to the AZ-1A are controlled by a low voltage

controller having an SPST switch (typically a thermostat). When there

is a call for heat, the relay is engaged to start the circulator, the amber

LED illuminates and the XX isolated end switch closes. This end

switch can be used to energize the boiler or other related controls.

When the thermostat is satisfied, the circulator and LED are turned off

and the end switch is opened.

AZ-1A INSTALLATION

1. Disconnect the electrical supply to the pump before installing the

AZ-1A controller.

2. Refer to applicable wiring diagram

– Figure 1: 2 wire thermostat

– Figure 2: 3 wire thermostat

– Figure 3: 4 wire thermostat

– Figure 4: Multiple zones

– Figure 5: Multiple zones with boiler pump

– Figure 6: Multiple pumps with one thermostat

Consult local representative for other configurations.

3. Remove the screw that holds the steel conduit box cover to the

pump.

4. Remove the conduit box cover. The AZ-1A assembly replaces the

conduit box cover.

5. If AZ-1A is being installed onto an already installed pump, discon-

nect the black and white motor leads from the power supply.

6. Position the plastic base for the AZ-1A onto the steel conduit box

with the warning/caution label to the rear of the pump.

7. Verify that the electrical rating of the AZ-1A matches the values

shown on the nameplate of the circulator.

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

ZoneTrol II

TM

Model AZ-1A

8. Make the electrical connections according to the wiring diagram

provided. Run the pump power wiring through one of the holes in

the metal conduit box. Do not attach conduit to the hole in the

plastic base. This hole is only for 24 volt control wiring. Use 14

AWG copper electrical wire with a minimum temperature rating of

90°C. Refer to your electrical code for wiring restrictions.

9. Run the thermostat wires through the grommet in the plastic base

and connect to the appropriate TR/TW terminals. Run the 24-volt

boiler control wires through the grommet in the plastic base and

connect to the XX terminals (See Fig. 3). Do not use the holes in

the metal conduit box for 24 volt control wiring. The holes in the

metal conduit box are for power wiring only.

10. Position the AZ-1A relay PC board in the plastic base with the

electronic components on the top.

Make sure that all pump

wiring connections are inside the box below the PC board.

Note that the hole in the PC board must line up with the mounting

hole in the plastic base.

11. Secure the AZ-1A PC board and plastic base to the conduit box

with one of the provided 8-32 screws.

12. Fasten the cover to the base using two of the provided 8-32

screws.

Multiple Zones (Figure 4)

When using multiple AZ-1A controls on a system with a boiler pump, each

controller should be connected to input power and its respective pump

as shown in Figures 1, 2, or 3, depending on style of thermostat(s).
Connect each thermostat to its respective AZ-1A. Wire the XX termi-

nals on each AZ-1A to the TT Controls on the Boiler.

Multiple Zones with Boiler Pump (Figure 5)

When using multiple AZ-1A controls on a system with a boiler pump, each

controller should be connected to input power and its respective pump

as shown in Figures 1, 2, or 3, depending on style of thermostat(s).
Connect each thermostat to its respective AZ-1A. Wire the XX ter-

minals to each zone AZ-1A to the T/R and T/W terminals on the Boiler

Pump AZ-1A. The XX terminals on the Boiler Pump AZ-1A are wired

to the TT Controls on the Boiler.

Multiple Pumps with One Thermostat (Figure 6)

When using AZ-1A controls on a system with multiple pumps and one

thermostat, each controller should be connected to input power and

its respective pump as shown in Figures 1, 2, or 3, depending on style

of thermostat.
Connect the thermostat to the first AZ-1A. Wire the AX AX terminals

of the first zone to the T/R and T/W terminals of the second AZ-1A.

Wire the XX terminals to the boiler TT control. Any number of addi-

tional pumps can be switched on by the same thermostat by

connecting the XX terminals to the T/R and T/W terminals of the next

AZ-1A.

WARNING: Electrical Shock Hazard

Disconnect and lock out the power before making electrical

connections. Failure to follow these instructions could result in

serious personal injury or death.

WARNING: Electrical Shock Hazard

Electrical connections are to be made by a qualified electri-

cian in accordance with all applicable codes, ordinances and

good practices. Failure to follow these instructions could result in

serious personal injury, death and/or property damage.

WARNING: Electrical Shock Hazard

Improper assembly could cause electrical shock and fire.

Failure to follow these instructions could result in serious personal

injury, death and/or property damage.

INSTRUCTION MANUAL

P86315B

Advertising