Bell & Gossett V58222C Tank Purge Valve – TPV User Manual

Tank purge valve – tpv, Instruction manual

Advertising
background image

Tank Purge Valve – TPV

WARNING: LABEL PART NO. V56873

INSTALLED IN THIS LOCATION

(UNDER BELL & GOSSETT). IF

MISSING, IT MUST BE REPLACED.

SAFETY 

INSTRUCTION

This safety alert symbol will be used in this manual to draw attention

to safety related instructions. When used, the safety alert symbol means

ATTENTION! BECOME  ALERT!  YOUR  SAFETY  IS  INVOLVED!

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A

SAFETY HAZARD.

INSTALLLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

OPERATIONAL LIMITS

WORKING PRESSURE & TEMPERATURE LIMITS

(SOLDER TYPE LIMITS FOR ANSI STD. B.16.18)

NPT

Maximum Operating Pressure 400 psig (2758 kPa)

Maximum Operating Temperature 250°F (121°C)

DESCRIPTION

The Bell & Gossett Tank Purge Valve (TPV) is a combination full port

ball type isolation valve and drain valve used to connect the system to

the expansion tank.  This  valve allows the tank to  be  drained  for  easy

servicing  or  tank  replacement  without  having  to  drain  the  system.

These valves are furnished standard with a drain valve with standard

5

/

8

" hose connection.

MAXIMUM

MAXIMUM

LIMITATIONS

LIMITATIONS

TYPE OF

1

/

2

" – 1"

1

1

/

4

" – 2"

SOLDER

PRESSURE

TEMP

PRESSURE

TEMP

PSI (kPa)

°F (°C)

PSI (kPa)

°F (°C)

95-5

300 (2069)

200 (93)

300 (2069)

175 (79)

TIN-

250 (1724) 225 (107)

250 (1724)

200 (93)

ANTIMONY

200 (1379) 250 (121)

175 (1207)

250 (121)

ISOLATION VALVE

SYSTEM

DRAIN VALVE

TANK

FIGURE 1

WARNING: Damage  to  the  Tank  Purge  Valve  or  failure  of 

solder sealing joints may occur if these operational limits are

exceeded. This can result in water leakage. Failure to follow this in-

struction can cause serious personal injury and/or property damage.

WARNING: Isolation valve must be in the open position with 

the handle inline with the valve body when the system is in

operation. Failure to follow these instructions may cause system to

over pressurize and can result in serious personal injury, death and

property damage.

WARNING: Drain  valve  must  be  in  the  closed  position

with  the  handle  perpendicular  to  the  valve  body  when  the

system  is  in  operation.  Failure  to  follow  these  instructions  can

cause property damage due to leakage through the drain valve.

NOTE: This product is not intended for use in potable water applications.

WARNING: California Proposition 65 Warning! This product contains chemicals known to the State of California
to cause cancer and birth defects or other reproductive harm.

INSTRUCTION MANUAL

V58222C

Advertising