9 Appendix

A

9.1

Installing the FMPS Power Module as a Stand-alone Unit

The following instructions are for installation of the FMPS power module in an independent application.

9.1.1

Installing the FMPS Power Module

1. Unpack and inspect the FMPS power module for damage. For technical support,

contact Alpha Technologies at 800 863 3364.

2. Select a suitable location for mounting the FMPS power module. Allow at least one

inch clearance above and below the power module for proper cooling. The FMPS
power module can be wall-mounted or mounted in a 19” or 23” equipment rack. See
Section 4 for details.

3. Connect the AC wiring. The FMPS power module can be hardwired or powered using

one of the AC power cord options. Connect AC service to the AC input block as
follows: (120Vac) Line (black), Neutral (white), and Safety Ground (green); (240Vac)
Line 1 (black), Line 2 (red), and Ground (green). Leave a 6” to 8” space under the
FMPS power module for servicing.

4. Connect the DC load and alarm wiring. Use of #16 AWG wire for DC wiring is

recommended. Connect the DC load blocks (red=positive, black=negative). Tighten
snug; do not over-tighten.
Pull open the alarm IDC connectors (small orange
connectors) and insert #24 AWG alarm wires into the connectors. Do not attempt to
remove the IDC connectors. Press the connectors shut to complete the connections.

5. Install one or two strings of batteries, if applicable.
6. Install the battery temperature probe wiring. The wiring is not polarity sensitive. Tape

the end of the sensor to the centermost battery.

7. Check all connections.
8. To verify that the unit is operational, apply AC power by a) plugging the unit into AC

power outlet, b) by turning on the AC feeder breaker, or c) by connecting the IEC
(option) to specified source.

Use plastic tie for AC
wiring strain relief

Insert wire and

close connector

Figure 15–FMPS power module connection details

9.1.2 FMPS

Operation

1. Verify no alarms are active and the green power indicator is lit (Table E).
2. Connect the DC load.
3. Secure the FMPS cover with a padlock or a wire utility tie.