CAUTION: to reduce risk of fire, use only 0.129mm2 (#26 AWG) or larger wire.

Terminal

Description

Default Name

Signal

Range

1 and 2; V2

Voltage Input 2

Charge Voltage

Pos (+)/Neg (-)

0-300Vdc

3 and 4; GP1*

General Input 1

GP1

Pos (+)/Neg (-)

0-300Vdc

5 and 6; GP2*

General Input 2

GP2

Pos (+)/Neg (-)

0-300Vdc

7 and 8; GP3*

General Input 3

GP3

Pos (+)/Neg (-)

0-300Vdc

9 and 10; GP4*

General Input 4

GP4

Pos (+)/Neg (-)

0-300Vdc

11 and 12; T1

Temp Input 1

T1

Pos (+)/Neg (-)

0-20Vdc

13 and 14; T2

Temp Input 2

T2

Pos (+)/Neg (-)

0-20Vdc

15 and 16; I2

Current Input 2

I2

Pos (+)/Neg (-)

±50mV

19 and 20; D1**

Digital Input 1

Distribution Fuse (Alarm)

N/A

Short or open

21 and 22; D2**

Digital Input 2

Distribution CB (Alarm)

N/A

Short or open

23 and 24; D3**

Digital Input 3

Battery CB (Alarm)

N/A

Short or open

25 and 26; D4**

Digital Input 4

Battery CB (Alarm)

N/A

Short or open

27, 28 and 29; K1***

Alarm Output 1 LVD1

NC/COM/NO 220Vdc,

0.4A

30, 31 and 32; K2***

Alarm Output 2 LVD2

NC/COM/NO 220Vdc,

0.4A

33, 34 and 35; K3***

Alarm Output 3 LVD3

NC/COM/NO 220Vdc,

0.4A

36, 37 and 38; K4***

Alarm Output 4

System Minor

NC/COM/NO

220Vdc, 0.4A

39, 40 and 41; K5***

Alarm Output 5

System Major

NC/COM/NO

220Vdc, 0.4A

42, 43 and 44; K6***

Alarm Output 6

AC Mains Hi-Low

NC/COM/NO

220Vdc, 0.4A

45, 46 and 47; K7***

Alarm Output 7

Not assigned

NC/COM/NO

220Vdc, 0.4A

48, 49 and 50; K8***

Alarm Output 8

Not assigned

NC/COM/NO

220Vdc, 0.4A

51, 52 and 53; K0****

Alarm Output 0

System Fail Output

NC/COM/NO 220Vdc,

0.4A

54 and 55; B PWR

Secondary Power

Secondary Power

Pos (+)/Neg (-)

90-300Vdc

56 and 57; A PWR

Power

Power

Pos (+)/Neg (-)

90-300Vdc

DCCT input; P3

Current Input 1

I1

Pos (+)/Neg (-);
Pwr (+)/Pwr (-)

±15Vdc, 100mA max.

Table A–Wiring connections

*

Bipolar (Voltage Input) is ±150Vdc, Unipolar Voltage (Input) is 0—300Vdc, Temp Probe is 0—20Vdc with power source.

**

See Table B for definitions of impedance levels.

***

Can be configured to de-energize on alarm (DOA) or energize on alarm (EOA).

****

System Fail output relay is fail-safe and will de-energize during an alarm condition.


NOTE: DCCT power output is protected against short circuits and is able to power four DCCTs.

To aid the user with installation, frequent reference is made to drawings located at the rear of this manual.
Custom configurations may be detailed within the Argus power system documentation package.

5.7.1

Programming the Digital Input

The digital input channels (terminals 19 through 26) can be programmed for “active high” or “active low.” Active
high indicates “alarm on the presence of a short circuit” and active low indicates “alarm on the removal of the
short circuit.”

NOTE: See CXC Software manual for detailed instruction on programming.

Impedance Level (Ohms)
Considered As “0” (Off)

Impedance Level (Ohms)
Considered As “1” (On)

> 1M

< 1

Table B–Digital input impedance level definitions