6 led, 5 cordex rectifier cxrf 48-300w, 1 led rectifier status indicator – Alpha Technologies Cordex CXCRF 48-300W User Manual

Page 17: 2 54v dc auxiliary output, Cordex rectifier cxrf 48-300w

Advertising
background image

0300072-J0 RevA

Page 13 of 46

2.6.4.6 LED

When the green LED is on, the LVD is active (closed).
When the LED is off, the LVD is not active (open).

2.6.5 Cordex Rectifier CXRF 48-300W

Figure 9 : Cordex Rectfier

2.6.5.1 LED

R

ECTIFIER

S

TATUS

I

NDICATOR

The LED indicates the status of the rectifier:

Green LED

Normal conditions

Orange LED

Stand-by (remote on/off)

Red LED

Low output voltage

Red blinking LED

Failure (mains, temperature, output short circuit)

2.6.5.2 54V

DC

A

UXILIARY

O

UTPUT

This auxiliary 54V output allows the user to start with a basic bulk shelf without any controller or distribution unit.

Thanks to the modular architecture the user can upgrade the system when the application requires battery back-

up, system monitoring or redundancy. The output power is limited to 300W.

Auxiliary Output

GND

+

-

Maximum conductor cross section: 2.0 mm² stranded (14AWG), maximum 8A current

The auxiliary output connector on the front is a 3-pole Phoenix contact MC 1,5/ 3-GF-3,81.

The mating connector must be a 3.81mm (0.150”) pitch, 3 positions. It can be ordered from Alpha Technologies.

Advertising