3 comp@s settings, 1 licence overview, Comp@s settings – Alpha Technologies Cordex CXCRF 48-300W User Manual
Page 33: Licence overview
0300072-J0 RevA
Page 29 of 46
Colour
Pulse freq.
(Hz)
State
Description
Green
Permanent
OK
Normal conditions : U
out
within specifications
Orange
Permanent
REMOTE_OFF Normal conditions: in standby = OFF
Red
Permanent
DC_NOT_OK
DC voltage is below minimum rated voltage (36 V)
Red
Flashing
(2)
MAJOR_FAULT
The power supply is interrupted by one of the following
causes:
•
AC voltage out of range ≥ 285 V
•
Internal temperature too high
•
Output short-circuit longer than 10 sec
Table 3 : Rectifier LED indication
4.3 Comp@s Settings
The following features are available with the Comp@s card only.
4.3.1 Licence Overview
The following 4 different Comp@s software licenses are available:
•
Basic license
•
Battery license
•
Asset management license
•
Modbus (in combination with Asset management license)