Specifications – Alpha Technologies 32-0-10A Fuse Panel User Manual

Page 5

Advertising
background image

SPECIFICATIONS FOR ARGUS TECHNOLOGIES’ FUSE PANEL MODEL 32-0-10A

A

RGU

S

TECHNOLOGIES

020-103-B1 Rev B

Output

Voltage:

24VDC (List Option 1 or 5)
48VDC (List Option 2 or 6)

Current Capacity:

30 Amps DC maximum per block of 16 fuses
60 Amps DC maximum if common feed used

Interrupting Capacity:

450 Amps maximum at 60VDC resistive

Individual Fuse Rating:

Type GMT fuse (0A to 15A) at 60VDC

Input

Voltage:

24VDC (List 1)
48VDC (List 2)
24VDC and 48VDC (List 5,6)

Current:

60 Amps DC maximum (List 1 or 2)
30 Amps DC maximum each for 24VDC and 48VDC (List 5 or 6)

M iscellaneous

Alarms:

Alarm indicator for any fuse in a group of 16, ABS

Weight:

0.9 kg (2 lb.)

Size:

44mm H x 432mm W x 158mm D (1.75” H x 17.0” W x 6.2” D)
[all dimensions do not include mounting brackets]

Mounting:

Standard equipment rack; 19” or 23”; flush or center

Recommended Connection Wire Sizes (as per UL / CSA)

Ambient Temp=30 deg C:

Input: #10 AWG
Output: User dependant

Recommended Application

To be intended for use in any DC power supply system that has outputs of 24VDC and/or 48VDC and
where the application requires from 1 to 32 alarm-equipped fused outputs ranging from 0A to 15A using
GMT-type miniature fuses. The total current drawn through this fuse panel shall not exceed the stated
specifications. The use of both 24VDC and 48VDC inputs/outputs concurrently is supported.

The above information is valid at the time of publication. Consult factory for up-to-date ordering information.

Specifications are subject to change without notice.