Specifications for Alpha Technologies DCP03 300A Distribution Center

020-702-B1 Rev C WC

System Output

Voltage:

24 or 48Vdc

Current:

≤300A (dc) m axim um

Distribution Breaker Ratings:

18-position, plug-in type (bullet terminals), AM-style, 5 to 100A

Connections

Load Connections:

18x sets 1/4”-20 studs on 5/8” centers (List 87)

14x sets 1/4”-20 studs on 5/8” centers (List 88)

[multiple pole breaker adapter: 3/8” holes on 1” centers]

Battery Terminations:

4x sets 1/4”-20 studs on 5/8” centers (List 88)

[multiple pole breaker adapter: 3/8” holes on 1” centers]

Rectifier Terminations:

Hot: 2x sets 3/8” holes on 1” centers

Return: 2x sets 3/8” holes on 1” centers

Ground Bar:

18x sets 1/4” holes on 5/8” centers

Alarm Connections:

#16 to #26 AWG (1.5 to 0.14mm

2

)

Communication:

Terminal blocks: internal I/O

DB (serial) connection(s): optional CXCI and CXCM2 I/O

RJ-12 Offset: CAN for optional ADIO or 8DIO

Access:

Front access after installation with 1RU required above panel for tooling

Miscellaneous

Size:

133mm H x 432mm W x 318mm D (5.23" H x 17.25" W x 12.5" D)

[does not include mounting brackets]

Mounting:

19” or 23”; flush or center (default)

Weight:

11.6 kg (25.6 lb.)

Environmental

Operating Temperature:

-40°C to +65°C (-40°F to +149°F)

-40°C to +55°C (-40°F to +131°F) de-rated when L71 (24V LVD) equipped

Humidity:

10 to 95% non-condensing

Elevation:

-500m to +4000m (-1640 feet to 13124 feet)

The above information is valid at the time of publication. Consult factory for up-to-date ordering information.

Specifications are subject to change without notice.