3 analog inputs, Voltage, Temperature sensor – Alpha Technologies CXPS 48-1.2-225 48 Vdc User Manual

Page 33: Current

Advertising
background image

053-691-B1 Rev E

Page 25 of 33

5.10.3 Analog inputs

CAUTION: Ensure that the correct polarity is used for all input cable terminations.

The analog input channels are used to monitor various types of electrical signals. Some of the analog channels

are reserved for specific signals, while others are designated as general-purpose inputs that accommodate

various types of analog signals.
The Battery Hot input terminal on the I/O board is factory wired to the battery system terminal. This is done so that

the batteries will provide power to the controller when the main power circuit is disconnected from the batteries.

Voltage

The Voltage Input #1 (V1) terminal is located on the shelf to provide connections to an optional secondary

voltage input. For example, this input can be terminated to the load side of an LVD contactor to monitor the

load voltage.
The Voltage Input #2 (V2) is wired internally to the rectifier output voltage of the shelf. This input is used as a

reference for system alarms such as a high voltage, and for controls such as a low voltage disconnect.

Temperature sensor

The Temperature Probe input channels (T1 and T2) provide connections for temperature sensors. A voltage

is supplied to these terminals for sensor measurements.

Current

The Current Input #1 terminal (I1) is factory wired to the battery shunt.