2 main rectifier modes, 1 output voltage modes, 2 output current/power modes – Alpha Technologies CXPS 48-1.2-225 48 Vdc User Manual

Page 37: 3 factory ranges and defaults, Main rectifier modes, Factory ranges and defaults

Advertising
background image

053-691-B1 Rev E

Page 29 of 33

7.2 Main rectifier modes

In addition to Main Rectifier States, there is a set of Main Rectifier Modes. These modes can be divided into two

categories as follows:

7.2.1 Output voltage modes

Voltage modes can be thought of as modes that, under software control, can directly adjust the output voltage.

There are processes that occur in the rectifier that can change the output voltage without software control, for

example when the rectifier is at the current limit. The following table lists the four output voltage modes and a

description of when they are active:

Output Voltage Modes

Active when…

Float

Output voltage is set to the float voltage setting.

Equalize

Output voltage is set to the equalize voltage setting.

Battery test

Output voltage is set to the battery test voltage setting.

Safe

Output voltage is set to the safe mode voltage setting.

Table D–Output voltage modes

7.2.2 Output current/power modes

The output current/power modes directly affect the output current and power. The following table lists the four

output current/power modes and a description of when they are active:

Output Current/Power Mode

Active when…

Temperature foldback mode

Output current and power limit have been reduced because of high

temperature of the heat sink or internal ambient temperature sensor.

AC foldback mode

Output current and power limit have been reduced because of low AC input

voltage. This reduces the risk of tripping an AC breaker because of increased

AC current draw as the AC voltage decreases.

Short circuit foldback mode

Output current limit has been reduced because of a short circuit at the output.

Internal fault foldback mode

Output current limit has been reduced because of an internal fault.

Table E–Output current/power modes

7.3 Factory ranges and defaults

The following table lists the rectifier settings/ranges/defaults. Values can be adjusted via the controller:

Setting

Range (minimum to maximum)

Default

Float (FL) voltage

48 – 58 V

54 V

Equalize (EQ) voltage

50 – 58 V

55 V

Battery Test (BT) voltage

44 – 52 V

46 V

Safe mode voltage

46 – 56 V

51.4 V

OVP

59 V, cannot be set below present system FL/EQ/BT

57 V

Current limit (CL)

23 – 100%

100%

Power limit (PL)

0 – 100%

100%

Module start delay

0 – 250 s

1 s

System start delay

0 – 600 s

0 s

Low voltage alarm (LVA)

42 – 52 V

44 V

High voltage alarm (HVA)

52 – 59 V

55.5 V