0 data management, 1 scte-hms configurable alarms, continued – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual

Page 52

Advertising
background image

52

745-814-B11-001, Rev. C (03/2014)

6.2.1 SCTE-HMS Configurable Alarms, continued

Table 6-3, Recommended Settings for DSM3 Series Analog Alarms

Analog Alarms and Common Settings

Analog Alarms

Description

Alarm

Enable

LOLO

LO

HI

HIHI

Deadband

psTotalStringVoltage

36V

Scaled representation of the full

battery string in 1/100 Volts units

0x0F

3300

3500

4520 4570

50

Individual Battery Voltage

Battery Voltage of 12V Battery in

1/100 Volts units

0x0F

1050

1150

1530 1550

20

psInputVoltage

120V

Scaled representation of the input

line voltage in 1/100 Volts units

0x0F

Varies by site. The XM3 will switch to standby at

nominal +15% -30%

220V

0x0F

psRMSCurrentIn

Scaled representation of the Power

Supply's RMS curent in 1/100 A

units

0x00

Set as desired per site

psPowerIn

Representation of the Power

Supply's input power in 1 W units

0x00

Set as desired per site

psFrequencyOut

Representation of Power Supply's

output frequency in 1/100 Hz units

0x00

Set as desired per site

psOutputVoltage

Scaled representation of the Power

Supply output voltage in 1/100

Volts units

0x0F

4300

4550

5050 5300

200

0x0F

5650

6000

6600 7000

200

0x0F

7800

8200

9150 9300

200

psPowerOut

Representation of Power Supply

output power in 1W units

0x00

It is recommended that psOutputCurrent be used

for output alarms.

psStringChargeCurrent

Battery string charge current,

scaled in 1/100 Amp units

0x0C

Disable

Disable 1200 1250

20

psStringDischargeCurrent

Scaled representation of battery

string discharge current. This is an

RMS value in 1/100 Amps

0x00

Set as desired per site

psStringFloat

Battery string float charge current,

scaled in 1/100 Amp units

0x0C

Disable

Disable 1200 1250

20

psOutputCurrent

15A

Scaled representation of Power

Supply RMS currnt in 1/100 Amp

units

0x0C

Disable

Disable 1650 1720

20

18A

0x0C

Disable

Disable 1980 2060

20

22A

0x0C

Disable

Disable 2420 2530

40

psTemperature

-40 to +80 degrees C

0x0F

Varies by site

docsIfDownChannelPower

The CM's receive RF power scaled

in 1/10 dBmV units

0x0F

-150

-10

10

150

15

docsIfCmStatusTxPower

The CM's transmit RF power

scaled in 1/10 dBmV units

0x0C

0

0

500

550

15

atiBBsysViewTimeInStandby

Time in seconds that the Power

Supply's inverter is currently

running due to outage or self test

0x0C

0

0

Set as

desired for

notification

of extended

outage

10

Alarms for Optional Generator

GenVBatIgnition

Scaled representation of the

generator's ignition battery in

1/100 Volts

0x0F

1150

1200

1500 1550

20

genEnclosureTemperature

Temperature inside generator's

enclosure in degrees C

0x09

-40

0

0

55

5

The following table displays the various analog alarms with common settings for the DSM3 Series

Communications Module.

6.0 Data Management