0 specifications – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual

Page 94

Advertising
background image

94

745-814-B11-001, Rev. C (03/2014)

11.0 Specifications

DSM3x

DSM3

DPM

Battery Monitoring:

Up to four strings of 36V batteries

Up to two strings of 36V batteries

Up to four strings of 36V

batteries; Smart AlphaGuard

(SAG) option required for

individual battery monitoring

Power System Management:

Up to five power supplies and an

AlphaGen generator are managed

from a single DSM3x including

coordinated battery charging, system

test and aggregated alarms

N/A

N/A

Management Protocol:

Standard ANSI/SCTE-HMS MIBs support basic power supply monitoring. Advanced diagnostics with

battery and power module analytics available via secure SNMP

Advanced Diagnostics

1

Intelligent Power Supply

Interface:

Power supply user interface displays advanced diagnostics including: DOCSIS modem upstream and

downstream RF levels, IP address assigned by network DHCP server, MAC address and firmware

versions, individual battery voltages to verify correct wire harness installation

Battery State of Health (Requires

AlphaAPPs option):

Power supply internal analytic diagnostics report when batteries should be serviced.

Battery String Runtime Remaining

Battery Life Remaining

Network Tools

QAM Constellation Diagram: Identify types of interference and distortion in downstream RF signal.

Microreflections Meter: Locate microreflections detected in Coax caused by physical impairments.

Utility Status & Events

AC Line Status

Utility Performance Status (outages, sags, surges, frequency)

Utility Events (24-hour and lifetime number of events)

Power Inverter State of Health:

Power supply internal diagnostics report if the power inverter requires service.

Reported Values: Inverter OK, Replace Inverter

Hardware

RF Cable Interface:

F-connector, female, 75 Ohm, connector angle better accommodates coax bend radius when installed in

some enclosures

Local Interface:

RJ-45, Ethernet, multi-mode operation

LED Indicators:

Ready/Alarm, Upstream registration, Downstream lock, AlphaBus activity, RF level, Link, CPE traffic, Battery

Sense harness correctly connected

I/O Control (DSM3x and DPM Only): 6-pin Molex: Digital input, Digital output, 5V, Common

AlphaBus:

RJ-11 offset tab: Multiple-power supply and AlphaGen communications

Battery Monitoring:

8-pin Molex battery string A/B and

8-pin Molex battery string C/D.

8-pin Molex battery string A/B

10-pin Molex battery string

A/B and C/D (SAG option)

Tamper:

NO or NC, software configurable, reads enclosure door magnetic switch

Environment

Operating Temperature:

-40 to 65°C / -40 to 149°F

Storage Temperature:

-40 to 85°C / -40 to 185°F

Humidity:

10 to 90% non-condensing

Regulatory Compliance:

FCC Part 15 Class A

EN 50083-2:2006 EMC requirements for CATV equipment

EN 62040-2:2006 Uninterruptable power supply EMC requirements, Category C2

Surge: IEEE 587, Category B3

RoHS: Directive 2002/95/EC

1

Advanced diagnostics are available through Alpha Certified network monitoring systems

Network Communications

DOCSIS (RF) Port Protocols:

IP (IPv4, IPv6), UDP, TCP, DHCP, TFTP, SNMPv1,SNMPv2c, SNMPv3, HTTP, SNTP

Ethernet Port:

HTTP Web interface for local on-site diagnosis.

MIBs:

Power supply (ANSI/SCTE 38-4)

Other SCTE-HMS MIBs as defined by the SCTE for power supply and generator status monitoring

Alpha proprietary advanced UPS diagnostics

Advertising