Factory ranges and defaults, 4 factory ranges and defaults – Alpha Technologies Cordex 125-4.4kW User Manual

Page 26

Advertising
background image

Argus Technologies Ltd.

010-589-C0 Rev A WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 12 of 16

6.4

Factory Ranges and Defaults

The following tables lists the rectifier settings/ranges/defaults; changes are made via the CXC:

Setting

Range (minimum to maximum)

Default

Float (FL) Voltage

90 – 160V

130.5V

Equalize (EQ) Voltage

90 – 160V

132.9V

Battery Test (BT) Voltage

90 – 160V

106.3V

OVP

See note below – 160V

137.8V

Current Limit (CL)

9 – 100%

100%

Power Limit (PL)

0 – 100%

100%

Module Start Delay

0 – 250s

1s

System Start Delay

0 – 600s

0s

Low Voltage Alarm (LVA)

90 – 160V

106.3V

High Voltage Alarm (HVA)

90 – 160V

134.1V

EQ Timeout

1 – 2399h

30h

BT Timeout

1 – 250h

8h

Softstart Ramp-rate

Normal/Fast Normal

CL/PL Alarm

Enable/Disable

Enable

Remote Shutdown

Enable/Disable

Enable

Ramp Test

Enable/Disable

Enable

Table C–Cordex 125-4.4kW factory ranges and defaults


NOTE: OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 118.9V.