AVTECH Flood Sensor (Spot) (RMA-FS2-SEN) User Manual

Flood sensor, Spot), Room alert

Advertising
background image

The Flood Sensor

(Spot)

is activated by liquid (i.e. water) bridging the adjustable sensor probes (A)

to make a consistent contact. The unit can detect water film from zero height (i.e sensors turned out

to make contact with the floor or surface) to 1/8” height (i.e. sensors turned all the way in). The unit

is factory adjusted to activate with 1/32” water film height which is satisfactory for most applications.

The three adhesive pads provide a gap between the case and the surface to admit water under the unit,

allowing for detection.

CAUTION: If the adhesive pads are removed completely, the Flood Sensor unit may form a seal with the surface. This could

prevent the sensor probes from detecting water until water rises high enough to enter through the top of the Flood Sensor.

If desired, the self-adhesive pad (B) feature may be used to secure the Flood Sensor device to a specific

area by peeling off the thin protective layer from each pad. This helps ensure that the Flood Sensor

remains in place when located on a mounted surface and is important if the surface vibrates or is

sloped, allowing for movement over time or when wet. Most facilities have a specific area that is close

to a water source or known to be a low spot and therefore collects water before other areas. With this

in mind, placement of the Flood Sensor in a specific area where flooding is expected to occur first or

known to occur is always the best choice.

Although the two sensor probes (A) may be adjusted to make contact with the surface, it is

recommended that a small gap be set between the sensors and the surface so undesired activation caused

by dampness, dirt film or placement on an inappropriate surface (i.e. metal) does not occur.

When flooding caused by water or another liquid occurs to create contact between the two adjustable

sensor probes (A) on the underside of the Flood Sensor, a switch is tripped open within the Flood Sensor.

The opening of this switch sends a low voltage signal to the Room Alert ID Box and generates an alarm

condition or status. When the flood condition is eliminated, the switch will reset and the alarm will clear.

Setup And Adjustments

The Flood Sensor comes pre-configured for immediate use. Simply connect the open end of the sensor

cable to an available set of contacts on the Room Alert ID Box and then place the Flood Sensor in the

desired location. The sensor cable can be extended if desired.

Flood Sensor

(Spot)

Instructions For Installing The Flood Sensor

AVTECH Software

Phone 401.628.1600

Sales 888.220.6700

Web AVTECH.com

Application Note

Room Alert

RMA-FS2-SEN