NXC-I/O10

Input/Output Control Card

NetLinx Control Cards and NetModules

NetLinx Control Cards can be installed in either the NXF CardFrame,
NI-4000, or in NetModules. This document provides basic specifications
and wiring information. For detailed information on the cards, refer to the
NetLinx CardFrame, Control Cards, and NetModules Instruction Manual
available on-line via www.amx.com.

NXC-I/O10 Specifications

The NXC-I/O10 Input/Output Control Card (FG 2021) provides 10
Input/Output channels with LED feedback.
It acts as a logic-level input and responds to switch closures or voltage level
(high/ low) changes.
The Switch (SW) and Voltage (VO) modes are set with on-board jumpers.
Note: The I/Os on this card are not dry closure; they are electronic switches
that float at 5V when Off. Therefore, they should not be expected to work in
situations that require true dry contact (or dry closure).
The I/Os will work with the AMX PC1, PC2, UPC20 and UPC20+.

Setting the Switch/Voltage Mode Jumpers:

The NXC-I/O10 responds to switch closures or voltage-level (high/low)
changes. Compatible I/O devices include the Power Control Sensor (PCS),
tape transports and limit switches. The inputs are set for SW mode
(closure) or VO mode, as described below:

Switch (SW) Mode - jumper pins 2 and 3 (default setting)

In SW mode, the NXC-I/O10 senses switch, relay contact closures, or
provides a logic-level output.
The 3-pin jumpers for each input should be set to SW before wiring inputs
to the Card.

• An "On" condition is triggered by contact closures or a logic low of 0 to

1.5 VDC.

• An "Off" condition is triggered by a logic high of 2.5 to 5 VDC; set the

associated I/O to switch mode.

When used for an output, each I/O port acts as a switch to ground (GND),
and is rated at 180 mA @ 12 VDC.
Note: In Switch mode, the A terminals are connected to the NetLinx
Controller's ground. Sources that require isolation from the Controller's
ground should use voltage mode, and provide switched DC power for
sensing as required.

Voltage (VO) Mode setting (Jumper pins 1 and 2)

In VO mode, the NXC-I/O10 senses high- and low-voltage states commonly
from AC or DC signals. This mode provides opto-isolation.
The 3-pin jumpers for each input should be set to VO before wiring inputs to
the Card.

• An "On" condition is triggered by DC levels from 2.5 to 28 VDC

(+ or -), or AC levels from 2.5 to 24 VAC.

• An "Off" condition is triggered by DC levels from 0 to 1.5 VDC (+ or -)

or AC levels from 0 to 1.5 VAC.

NXC-I/O10 Channel Assignments:

Channels 1-10 represent I/O channels 1-10.

FIG. 1 NXC-I/O10 Control card

NXC-I/O10 (FG 2021) Specifications

Power Requirements:

180 mA @ 12 VDC

Operation:

I/O 1-10: 10 Input/Output channels

Status LEDs:

10 yellow LEDs light to show ON status activity
(1 per channel).

Modes:

Switch: Senses switch or relay contact

closures or provides a logic-level output.

Voltage: Senses high- and low-voltage states.

Voltage clamp settings: • 12 V mode (default): Clamps any voltage

connected to I/O ports 1-10 to 12 V.

VO mode: Use for connections that will draw

more than 12 V.

Connections/wiring:

Two 10-pin 3.5 mm captive-screw terminals

DEVICE_ID: $010b

SW/VO jumpers (J1 - J15)

V-Clamp +12V/open

SW/VO jumpers (J16 - J30)

jumper (J31)

Status LEDs

FIG. 2 Switch (SW) Mode - jumper pins 2 and 3 (default setting)

FIG. 3 Voltage (VO) Mode setting (Jumper pins 1 and 2)