INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) IOM-DA5

11/13

I. DESCRIPTION AND SCOPE

The Model DA5 is a spring operated back pressure regulator used to control upstream (inlet or P1) pressure. Sizes
are 1/2" (DN15), 3/4" (DN20), 1" (DN25), 1 1/4" (DN32), 1 1/2" (DN40), 2" (DN50), 2 1/2" (DN65), 3" (DN80) and
4" (DN100). With proper trim uti li za tion, the unit is suitable for liquid, gaseous, or steam service. The Model DA5
is available in a more common “reverse” fl ow direction arrangement, that is balanced against outlet pressure varia-
tions, and a “standard” fl ow direction arrangement that is unbalanced. Refer to Technical Bulletin DA5-TB for design
conditions and selection rec om men da tions. (NOTE: This product was formerly iden ti fi ed as a Model D5 or Type V;
a Model DA5, D5 and Type V are one and the same product.)

MODEL DA5

DA5 - DIRECT-ACTING, SPRING LOADED

BACK PRESSURE REGULATOR

SECTION I

II. REFERENCES

Refer to Technical Bulletin DA5-TB and DAG-TB for
tech ni cal specifi cations of a Model DA5 regulator.

ABBREVIATIONS

CCW – Counter

Clockwise

CW –

Clockwise

ITA

– Inner Trim Assembly

III. INSTALLATION

4. Install block valves and pressure gauges to pro-

vide means for adjustment, operation, bypass,
or removal of the regulator. A pipeline strainer is
recommended upstream of inlet port to remove
typical pipe line debris from entering valve and
damaging internal “soft goods”, primarily the dy-
namic side seal and V-TFE seat when applied.

5. Upstream Sensing Installation Considerations

– Internal or External Sensing:
a. The regulator may be installed with internal

or external sensing. Unless otherwise spec-
i fi ed, the regulator is supplied by the factory
with internal sensing. The regulator may be
con vert ed in the fi eld to external sensing. (See
Section VII maintenance, Part H – Converting
Internal/External Sensing.

b. Reference DAG-TB, Table DAG-12 for rec-

om men da tions for applying external pressure
sensing.

c. For internal sensing, no external line is re-

quired. For external sensing, use an external
control line. The line is connected from the
port 1/4" (DN8) NPT on the side of the body
di a phragm fl ange (see following schematic)
to a pressure tap upstream of the regulator.

SECTION III

SECTION II

CAUTION

For welded installations, all internal trim parts, seals and
diaphragm(s) must be removed from reg u la tor body prior to
welding into pipeline. The heat of fusion welding will dam-
age non-metallic parts if not re moved. NOTE: This does
not apply to units equipped with extended pipe nip ples.

1. Install per direction of fl ow arrow indicated on body,

or "IN" and "OUT" markings.

2. Regulator may be rotated around pipe axis 360

degrees. For ease of maintenance, the rec om -
mend ed position is with the spring chamber (4)
upwards. In liquid service it is recommended that
the spring cham ber be oriented down wards, and
that a cus tom er supplied and installed vent valve
be pro vid ed at the external sensing connection
to bleed-off trapped gas/air under the diaphragm
during initial startup.

3. Provide space below, above, and around reg u la tor

for removal of parts during maintenance.