VIII. L o o p I n s t a l l a t i o n :

The vehicle detection characteristics of an inductive loop detector are greatly influenced by the loop size
and proximity to moving metal objects such as gates. Vehicles such as small motorcycles and high bed
trucks can be reliably detected if the proper size loop is selected. If the loop is placed too close to a
moving metal gate, the detector may detect the gate. The diagram below is intended as a reference for
the dimensions that will influence the detection characteristics.

General Rules:

1. The detection height of a loop is 2/3 the shortest leg (A

or B) of the loop. Example: Short leg = 6 feet,
Detection Height = 4 feet.

2. As the length of leg A is increased, distance C must

also increase.

3. For reliable detection of small motorcycles, legs A and

B should not exceed 6 feet.

L o o p I n s t a l l a t i o n - S a w C u t T y p e

1

Mark the loop layout on the pavement. Remove sharp inside corners that can damage the loop wire insulation.

2

Set the saw to cut to a depth (typically 2" to 2.5") that ensures a minimum of 1" from the top of the wire to pavement
surface. The saw cut width should be larger than the wire diameter to avoid damage to the wire insulation when pla ced
in the saw slot. Cut the loop and feeder slots. Remove all debris from the saw slot with compressed air. Check that the
bottom of the slot is smooth.

3

It is highly recommended that a continuous length of wire be used to form the loop and feeder to the detector. Loop
wire is typically 14, 16, 18, or 20 AWG with cross-linked polyethylene insulation. Use a wood stick or roller to insert the
wire to the bottom of the saw slot (do not use sharp objects). Wrap the wire in the loop saw slot until the desired
number of turns is reached. Each turn of wire must lay flat on top of the previous turn.

4

The wire must be twisted together a minimum of 6 twists per foot from the end of the saw slot to the detector.

5

The wire must be held firmly in the slot with 1" pieces of backer rod every 1 to 2 feet. This prevents the wire from
floating when the loop sealant is applied.

6

Apply the sealant. The sealant selected should have good adhering properties with contraction and expansion
characteristics similar to those of the pavement material.

O P E R A T I N G I N S T R U C T I O N S F O R

Model BXC Series

SINGLE CHANNEL LOOP DETECTOR

I.

General:

Please verify source voltage before applying power. The model designation indicates the input power
required and Fail-Safe / Fail-Secure configuration for the detector as follows.

Model BXC-x-x-x

Blank = Fail-Safe, S = Fail-Secure

Blank = Conventional Outputs

E = Euro Outputs

3 = 120 VAC

4 = 12 VDC / 24 VDC / 24 VAC

8 = 240 VAC

The detector is factory configured for either Fail-Safe or Fail-Secure operation (see unit side label). The
output state of each output relay in either Fail-Safe or Fail-Secure mode is listed in the table below.

Relay

Fail-Safe

Fail-Secure

Power Failure

Loop Failure

Power Failure

Loop Failure

A

Call

Call

No Call

No Call

B

No Call

No Call

No Call

No Call

II.

Indicators and Controls:

i.

Power / Detect / Fail LEDs:

The detector has one green and two red LED indicators that are used to provide an indication
of the detector’s power status, output state, and/or loop failure conditions. The table below lists the
various indications and their meanings.

Status

POWER LED

DETECT LED

LOOP FAIL LED

Off

No power or low power

Output(s) Off

Loop OK

On

Normal power to detector

Output(s) On

Open Loop

Flash

N/A

4 Hz - Two second timing

delay activated

1 Hz - Shorted Loop

3 Hz - Prior Loop Failure

Note: If the supply voltage drops below 75% of the nominal level, the POWER LED will turn off, providing a
visual indication of low supply voltage. Model BXC detectors will operate with supply voltage as low as 70%
of nominal supply voltage.

ii. Front Panel DIP Switches:

Switch

ON

OFF

Factory Default

1

Frequency

(See Table under Frequency Section)

OFF

2

OFF

3

Two Second Delay

No Delay

OFF

4

Sensitivity Boost

No Boost

OFF

5

Sensitivity

(See Table under Sensitivity Section)

ON

6

OFF

7

Exit Pulse or Fault Output

B Relay

Entry Pulse or Presence Output

B Relay

OFF

8

Presence Mode B Relay

Pulse Mode B Relay

OFF

A =

6 ft

9 ft

12 ft

15 ft

18 ft

21 ft

C =

3 ft

4 ft

4.5 ft

5 ft

5.5 ft

6 ft

Reno A & E

4655 Aircenter Circle

Reno, NV 89502-5948 USA

Telephone: (775) 826-2020

Fax: (775) 826-9191

Website: www.renoae.com

E-mail: [email protected]

Engineering Excellence!

Reno A & E

4655 Aircenter Circle

Reno, NV 89502-5948 USA

Telephone: (775) 826-2020

Fax: (775) 826-9191

Website: www.renoae.com

E-mail: [email protected]

Engineering Excellence!

1

3

1/8" to 1/4" SAW SLOT

THE WIRE IS
CONTINUOUSLY WOUND
IN THE LOOP SAW SLOT
FOR THE REQUIRED
NUMBER OF TURNS (2
turns shown)

turn 2

turn 1

REMOVE SHARP
INSIDE CORNERS

FEEDER SLOT

END OF SAW CUT

4

THE WIRES MUST BE
TWISTED TOGETHER
6 TWISTS PER FOOT
FROM THE END OF
THE SAW CUT TO
THE DETECTOR

Recommended Loop Wire:

Reno LW-120 for 1/8" slots

Reno LW-116-S for 1/4" slots

ROAD SURFACE

MIN

1"

SAW SLOT

SEALANT

BACKER ROD
1" piece
spaced about
every 1'

LOOP WIRE

3 TURNS

2

6

5

LOOP PERIMETER NUMBER OF TURNS

10 feet - 13 feet

5

14 feet - 26 feet

4

27 feet - 45 feet

3

46 feet - 100 feet

2

100 feet and up

1

A

B

C

A = Loop dimension parallel to the gate

B = Loop dimension perpendicular to the gate

C = Distance of the loop from the gate

SLIDE GATE