COMPACT SUBCOOL/SUPERHEAT

CALCULATOR

TO GET SATURATION TEMPERATURE WHEN

SATURATION PRESSURE IS KNOWN (PT CHART)

1. Press the POWER ( ) button.
2. Use ▲ and ▼ to display the desired refrigerant.
3. Press ENTER.
4. Press any ARROW button to display the pressure, then use

▲ or ▼ to adjust the saturated pressure.
NOTE: To change the pressure quickly, hold the DOWN ARROW

(▼) button.
5. Read the saturated temperature next to the saturated pressure.
NOTE: For refrigerants that have glide, use the SH/SC

button to toggle between Bubble (BBL) and Dew Point (DP) tem-

peratures.

TO GET SUPERHEAT OR SUBCOOL WHEN THE

SATURATION PRESSURE IS KNOWN

To get superheat, use the low (suction) side saturated pressure

and use a tube on the suction side of the compressor for the actual

temperature.
To get subcool, use the high side saturated pressure and use a

tube close to the outlet side of the condenser for the actual

temperature.
1. Press the POWER ( ) button.
2. Use ▲ or ▼ button to display the system’s refrigerant.
3. Press ENTER.
4. Press any ARROW button to display the pressure, then use
▲ OR ▼ to adjust the saturated pressure.
NOTE: To change the pressure quickly, hold the DOWN ARROW

(▼) button.
5. Insert thermocouple clamp plug into side of unit.
6. Clamp thermocouple onto appropriate tube.
7. Press SH/SC to toggle between superheat or subcool

temperature.
8. Once the temperature has stabilized, read the superheat or

subcool temperature.
NOTE: The unit will not display a negative superheat or subcool

temperature. It will display -- instead. Check the side you are read-

ing your pressure on and the location of the thermocouple clamp.

ADDITIONAL FUNCTIONS
Hold Function

To freeze the temperature reading from the thermocouple on the
screen, press HOLD.