Installation and Quick Start

1

How to Avoid Equipment Damage

Disconnect UPS
power

You do not need to turn off a Symmetra

®

or a Silcon

®

model

UPS to install the Management Card.

Smart-UPS

1. Turn off the

equipment that
connects to the
UPS.

2. Disconnect the

UPS from its AC
input source.

3. Press the OFF

button on the
UPS for
approximately
five seconds to
turn off the DC
(battery) power.

Matrix-UPS

1. Turn off the

equipment that
connects to the
UPS.

2. Turn off the

circuit breaker on
the rear panel of
the UPS.

Disconnect
chassis power

Make sure that any Expansion Chassis or Triple Expansion
Chassis is disconnected from all power: disconnect the chassis
cable from the

UPS

and, if the

AC

-to-

DC

Adapter (AP9505)

option is used, disconnect the adapter from the chassis.

Caution

Damage to the UPS or APC Network Management
Card (AP9617 or AP9618) can result if you do not
remove all AC and DC power from a Smart-UPS

®

or Matrix-UPS

®

, an Expansion Chassis, or a Triple

Expansion Chassis before you install the
Management Card.