System Sensor DH100 Replacement Detector Board User Manual

System Sensor Equipment

Advertising
background image

Replacement Detector Boards

Ionization Detector Board: part number A5052

Photoelectric 2-Wire Detector Board: part number A5180

Photoelectric 4-Wire Detector Board: part number A5190

NOTE: PHOTOELECTRIC DETECTOR BOARDS CAN ONLY
BE INSTALLED IN PHOTOELECTRIC DUCT SMOKE
DETECTOR MODELS; IONIZATION DETECTOR BOARDS
CAN ONLY BE INSTALLED IN IONIZATION DUCT SMOKE
DETECTOR MODELS.
IMPROPER INSTALLATION WILL VOID ALL AGENCY APPROVALS.

Detector Board Replacement Instructions
1. Notify the proper authorities that the smoke detector system is undergoing

maintenance and that the detector will temporarily be out of service.

2. Turn off power to the duct smoke detector.

3. Remove the two detector board mounting screws.

Retain screws for installation of new board.

4. Pull gently on the board to remove it from the detector housing.

5. Align the board mounting features, holes, and interconnect terminals

with the features on the duct smoke detector housing.

6. Push the board into place.

7. Secure the board with the two board mounting screws.

8. Perform the detector checks as outlined in sections 6.2.1 and 6.2.2.1 of the Installation and Maintenance

Instructions to ensure proper detector operation. The tests performed must include:

A. Visually check to see the green power LED blinks once every ten seconds, indicating power to the duct

smoke detector. If the green LED does not flash, the detector lacks power (check wiring, panel or power
supply), the detector board is missing (install), or the unit is defective (return for replacement).

B. Perform the magnet test to initiate an alarm condition. Reset the detector using the local reset button,

remote accessory or system control panel.

Return all ionization boards to System Sensor for proper disposal: System Sensor
3825 Ohio Avenue
St. Charles, IL 60174

For additional assistance in this process or questions, please contact System Sensor Technical Service at

800-SENSOR2 (800-736-7672).

D100-71-00 1 I56-1359-01

DH100 Series Duct Smoke Detector

Replacement Detector Board

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

A5180/A5190: Photoelectric

Detector Board

A5052: Ionization

Detector Board

Advertising