Output specifications (sink type) – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 3

Advertising
background image

3

„ Output Specifications (Sink type)

‹Output Circuit (Sink type)

• Since the output terminals are not electrically protected, an output line might be short-

circuited or a connection fault might damage the GP unit. Please install an applicable fuse to
prevent an overload in the circuit, if necessary.

Rated Voltage

DC 24V

Rated Voltage Range

DC 20.4V to DC 28.8V

Output Method

Sink Output

Maximum Load Voltage

0.2A /point, 0.4A /common

Output Voltage Drop

1.5V or less

Output Delay
Time

OFF to ON

1ms or less

ON to OFF

1ms or less

Voltage Leakage (when OFF)

0.1mA or less

Clamp Voltage

39V ± 1V

Type of Output

Transistor Output

Common Lines

1

Common Design

2 points/1 common line

External Connection

12-pin connector (also used for Input)

Output Protection Type

Output is unprotected

Internal Fuse

1.5A, 125V DIP fuse (not replaceable)

Surge Control Circuit

Zener diode

Output Points

2

Output Signal Display

No LED indicators

Status Display Element

None

Isolation Method

Photocoupler Isolation

External Power Supply

DC 24V

L

L

+24V B1

0V A1

Internal Circuit

OUT1 A2

Internal Circuit

OUT0 B2

Fuse
1.5A

+

-

DC 24V
External Power

Advertising