Flex network specifications, Flex network interface (connector), Flex network data transfer settings – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 2: Flex network communication cable

Advertising
background image

2

FLEX NETWORK Specifications

„ FLEX NETWORK Interface (Connector)

„ FLEX NETWORK Data Transfer Settings

„ FLEX NETWORK Communication Cable

The following cables are used for connection to the FLEX NETWORK unit.

B

FLEX NETWORK
Interface

Used to connect the FLEX NETWORK I/O unit or
analog unit, etc.

C

FLEX NETWORK
Communication Status LED

This LED indicates the communication status of the
FLEX NETWORK.

Status LED

Indicates

RUN (Green)

Turns on when Communication
is enabled.

ERR (Red)

Turns on when failure occurs in
connected I/O Unit.

Applicable connector

284510-6 <Tyco Electronics AMP.>

Pin Arrangement

Signal Name

Description

1

TR+

CH1 communication data

2

TR-

CH1 communication data

3

SLD

CH1 cable, shielded wire

4

TR+

CH2 communication data

5

TR-

CH2 communication data

6

SLD

CH2 cable, shielded wire

Communication Type

1:N

Connection Method

Multi Drop

Transfer Distance

At 6Mbps 200m per CH, at 12Mbps100m per CH

Transfer Method

During cyclic period, distributed transmission, Half-duplex

Transfer Speed

6Mbps, 12Mbps

Transfer I/F

Differential method, Pulse transfer resistance

Error Check

Format check, bit check, CRC-12 check

No. of Stations

63 stations max., Bit variable input: 512 points

*1

, Bit

variable output: 512 points

*1

, Integer variable input: 128

points

*2

, Integer variable output: 128 points

*2

(depending on type of units used.)

*1

When using GP-Pro EX under Ver.2.50, Bit variable enables to input/output 256 points.

*2

When using GP-Pro EX under Ver.2.50, Integer variable enables to input/output 64 points.

Model

Length per Unit

FN-CABLE2010-31-MS

10m

FN-CABLE2050-31-MS

50m

FN-CABLE2200-31-MS

200m

6 5 4 3 2 1

(Cable connection side)