Relevant Standards

These devices have been manufactured in accordance with:

Standard EN 60079-0 (2009) and IEC 60079-0 Ed6 (2011): Explosive

atmospheres - Part 0: Equipment - General requirements.

Standard EN 60079-15 (2010) and IEC 60079-15 Ed4 (2010): Explosive

atmospheres - Part 15: Equipment protection by type of protection “n”.

Standard EN 60079-31 (2009) and IEC 60079-31 Ed1 (2008): Explosive

atmospheres - Part 31: Equipment dust ignition protection by enclosure
“t”.

Relevant products

These recommendations relate to graphic panels intended for installation in
areas where explosive atmospheres may occur (Zones 2/22) for Category 3G
or 3D equipment (Category 3: normal level of protection - G: Gas - D: Dust).

DANGER

POTENTIAL FOR EXPLOSION

Install, use, and maintain these modules in accordance with:

Standard IEC 60079-14 Ed4 (2007): Explosive atmospheres - Part 14:

Electrical installations design, selection and erection.

Standard EN 60079-17 (2007): Inspection and maintenance of

electrical installations in hazardous areas.

Standard EN 61241-14 (2004): Electrical apparatus for use in the

presence of combustible dust, Part 14: Electrical apparatus protected
by enclosures. Selection, installation and maintenance.

Edicts, by-laws, laws, directives, circulars, standards, regulations and

any other document relating to where the apparatus is installed.

Failure to follow these instructions will result in death or serious injury.