Installations, Installation requirements – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 3

Advertising
background image

3

Installations

1.

Installation Requirements

• In order to ensure proper serviceability,

operability and airflow, provide space
between the HTB and structural objects or
other parts as the figure shows.

C

Field bus
interface

A 9-pin plug D-SUB connector is used to connect the interface
module to a CANopen field bus. This bus is not insulated internally.

Recommended cable connector:
CiA-recommended CANopen (CiA DR-303-1) -compatible DSUB
9-pin connector (DIN41652) .
Recommended network cable:
CiA-recommended CANopen (CiA DR-303-1) -compatible twisted
pair cables with shield.

Note: Please use your own cables or cable connectors with

your guarantee.

D Electrical supply

Interface

Terminal for an external 24 VDC supply of the HTB.

E Indicator LED

F

In/Output Terminals

Input/Output terminals.

G Hook

A hook to fix HTB on the DIN rail.

H

Extension
Connector

For connecting EX modules; maximum number of EX modules
that can be connected is 7.

Contacts

Signal

Description

1

-

-

2

CAN_L

CAN-L bus line

3

CAN_GND

CAN Ground

4

-

-

5

-

-

6

GND

Ground(Common with CAN_GND)

7

CAN_H

CAN-H bus line

8

-

-

9

-

-

Shell

FG

Frame Ground

LED

Status

PWR

Indicates the presence of a 24 VDC power supply to HTB.

RUN
ERR

2 (RUN) and 3 (ERR) show the data exchange status
between the communication units that can transmit data.

I0 - I11
Q0 - Q7

Reflect the I/O status of HTB’s integrated I/O.

20 [0.79]

80 [3.15]

Unit : mm [in.]

20 [0.79]

20 [0.79]

40
[1.57]

40
[1.57]

20 [0.79]

Advertising