55

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[Alm]
[`Set]
Alarm Menu

[`A;ty]
[ A.ty]

Alarm (1 to 4)

Alarm Type

Select whether the

alarm trigger is a fixed

value or will track the

set point.

[`oFF]

Off (62)

[PR;AL]

Process Alarm (76)

Off

Instance 1
Map 1 Map 2

1508

1908

Offset to next

instance (Map

1 & Map 2)

equals +60

0x6D (109)

1 to 4

0xF (15)

20

9015

uint
RWES

[`Sr;A]
[ Sr.A]

Alarm (1 to 4)

Alarm Source

Select what will trigger

this alarm.

[``Ai]

Analog Input (142)

- - - -

Instance 1
Map 1 Map 2

1512

1912

Offset to next

instance (Map

1 & Map 2)

equals +60

0x6D (109)

1 to 4

0x11 (17)

21

9017

uint
RWES

[`A;hy]
[ A.hy]

Alarm (1 to 4)

Alarm Hysteresis

Set the hysteresis for

an alarm. This deter-

mines how far into the

safe region the process

value needs to move

before the alarm can be

cleared.

0.001 to 9,999.000°F or units
0.001 to 5,555.000°C

1.0°F or

units

1.0°C

Instance 1
Map 1 Map 2

1484

1884

Offset to next

instance (Map

1 equals +50,

for Map 2

equals +60)

0x6D (109)

1 to 4

3

24

9003

float
RWES

[`A;Lg]
[ A.Lg]

Alarm (1 to 4)

Alarm Logic

Select what the output

condition will be during

the alarm state.

[`AL;C]

Close On Alarm (17)

[`AL;o]

Open On Alarm (66)

Close On

Alarm

Instance 1
Map 1 Map 2

1488

1888

Offset to next

instance (Map

1 equals +50,

for Map 2

equals +60)

0x6D (109)

1 to 4

5

25

9005

uint
RWES

[`A;Sd]
[ A.Sd]

Alarm (1 to 4)

Alarm Sides

Select which side or

sides will trigger this

alarm.

[both]

Both (13)

[high]

High (37)

[LoW]

Low (53)

Both

Instance 1
Map 1 Map 2

1486

1886

Offset to next

instance (Map

1 equals +50,

for Map 2

equals +60)

0x6D (109)

1 to 4

4

26

9004

uint
RWES

Note: