GENERAL DESCRIPTION:

Toxalert’s refrigerant sensor/transmitter is designed for
use in conjunction with Toxalert and other standard 4 to
20 mA loop or voltage controllers.
The Tox-Refrig/ANA refrigerant sensor is a metal oxide
semi-conductor (solid state) cell with
extremely long element life. The Tox-Refrig/ANA
transducer requires 24 vdc power and has a 4 to 20 mA
output current which is proportional to the refrigerant
gas concentration. The cover plate inside the expolsion
proof enclosure contains: test points (which are
receptables for voltage meter probes) for measurement
of sensor signal, heater voltage; visual indicator for
sensor check; and potentiometers adjustments for zero
and span.

BACKGROUND:

ANSI/ASHRAE Standard 15-1994, Safety Code for Mechanical Refrigeration, lays out requirements
for the monitoring of mechanical equipment rooms containing refrigeration equipment. Paragraph
8.13.2 reads in part:

“Each machinery room shall contain a detector, located in an area where refrigerant from a leak
will concentrate, which shall actuate an alarm and mechanical ventilation in accordance with
8.13.4 at a value not greater than the corresponding TLV-TWA (or toxicity measure consistent
therewith).”

FEATURES

• Sensitivity check indicator

• Current output may be read as a

• Low voltage circuits

voltage during calibration

• 4 to 20 on A output signal

• Sensor failure indicator

• Meets ASHRAE Std. 15-1994

• Interfaces directly to DDC systems

• Explosion Proof Housing

REFRIGERANT SENSOR

MODEL TOX-REFRIG/ANA

REFRIGERANTS MONITORED

R-11

R-22

R-123

R-141b

R-500

R-12

R-113

R-134a

R-152a

R-502

*Many Others*