Sterling GG User Manual

4" combustion air inlet kit

Advertising
background image

Improper installation, adjustment, alteration, service or maintenance can cause

p ro p e r t y d a m ag e , i n j u r y o r d e a t h . R e a d t h i s s u p p l e m e n t a n d t h e u n i t h e a t e r i n s t a l l a t i o n ,
operating, and maintenance instructions thoroughly before installing or servicing this equipment.

The location of the vent terminal must be in
accordance with the National Fuel Gas Code ANSI
Z223.1 (NFPA 54) in the U.S. or the Natural Gas
Installation Code CSA-B149.1 or the Propane
Gas Installation Code CSA-B149.2 in Canada.
Minimum clearances are shown in Table 1 and
Figures 4, 5 and 6.

This Combustion Air Inlet Kit utilizes one 4 inch
termination in which both the discharge fl ue gas
and the combustion air inlet pass.

KIT CONTENTS (Figure 1)
(#1) Part No. 11J37R08571-001
(1) Flue Vent Terminal

(#2) Part No. 11507R06601
(1) Combustion Air Inlet Box Assembly
(see Figure 2 for dimensional data)

(#3) Part No. 11257R06665
(1) Air Inlet Screen

(#4) Part No. 11507R06693
(1) Defl ector Disk

(#5) Part No. 11257R08331
(1) Inlet Air Collar - 4"

(#6) Part No. 11J37R08332
(1) Inlet Air Collar Gasket

Also Included:
(1) Part No. J30-08579
Installation Instructions

(1) Part No. 11H03R03612-002
Tube of High Temp Silicone Sealant

(1) Part No. 11262R08614-004
Access Panel Gasket - 68.5"

01/14

ASX7-4-IOM-5

J30-08579

Figure 2 - Combustion Air Inlet Box Dimensions

Figure 1 - Kit Contents

D8618B

INSTALLATION INSTRUCTIONS

4" COMBUSTION AIR INLET KIT

TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS

UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION

For 30,000 to 75,000 BTU/HR

SUPPLEMENT TO UNIT INSTALLATION INSTRUCTIONS

GG-IOM & 5S6935

D6875B