Compressor

The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should

provide years of satisfactory operating service.
Should the refrigerant charge be lost, recharging ports (access fittings) on the suction and discharge sides of the

compressor are provided for recharging and/or checking suction and discharge pressures.
Under no circumstances should the access fitting covers be loosened, removed or tampered with.
Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system.
Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for

recharging the air conditioner.

Inlet Air Filter

Proper maintenance of the inlet air filter, located behind the front cover, will assure normal operation of the air

conditioner. If filter maintenance is delayed or ignored, the maximum ambient temperatures under which the unit is

designed to operate will be decreased.
If the compressor’s operating temperature increases above designed conditions due to a dirty or clogged filter (or

plugged condenser coil), the air conditioner’s compressor will stop operating due to actuation of the thermal overload

cut-out switch located on the compressor housing. As soon as the compressor temperature has dropped to within

the switch’s cut-in setting, the compressor will restart automatically. However, the above condition will continue to

take place until the filter or coil has been cleaned. It is recommended that power to the air conditioner be interrupted

intentionally when abnormally high compressor operating temperature causes automatic shut-down of the unit. The

above described shutdown is symptomatic of a clogged or dirty filter, thus causing a reduction in cooling air flow

across the surface of the compressor and condenser coil.
Do not run the air conditioner for extended periods of time with the filter removed. Particles of dust, lint, etc., can plug

the fins of the condenser coil which will give the same reaction as a plugged filter. The condenser coil is not visible

through the filter opening, so protect it with a filter.
Continued operation under the above conditions can and will damage and shorten compressor life. The air

conditioner is available with an easily removable inlet filter to facilitate necessary cleaning. There should be no reason

to neglect this necessary maintenance.

How To Remove, Clean or Install a New Inlet Air Filter

RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding

capacity and a minimum amount of resistance to air flow. Because they are constructed entirely of aluminum they are

lightweight and easy to service. Optimum filter performance is maintained by recoating the filters after washing with

RP Super Filter Coat adhesive. To achieve maximum performance from your air handling equipment, air filters should

be cleaned on a regular basis.
The inlet air filter is located behind the front cover. To access filter, pull ring protruding from slot in bottom of front

cover. The filter may now be cleaned or new filter installed.
Cleaning Instructions:

1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.
2. After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage.
3. Recoat the filters with RP Super Filter Coat adhesive. When spraying filter do so from both sides for

maximum concentration of adhesive.