INSTALLATION INSTRUCTIONS

1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See

HANDLING AND TESTING THE AIR CONDITIONER on page 3.

2. Using the cutout dimensions shown page 5 in this manual, prepare the air “IN” and air “OUT” openings,

and mounting bolt hole pattern for the enclosure.

3. Using the gasket kit provided, install gaskets to air conditioner.
4. Mount air conditioner on enclosure using mounting bolts and screws provided. “EZ” mount tabs

can be used to hold unit on enclosure while mounting in place. Allow unit to remain upright for a

during operation.

5. When routing the drain tube, caution should be taken to keep it from kinking or being elevated above

the exit point of the air conditioner. The drain tube must be on a continuous downward slope. A

slight elevation of the tube could result in secondary trap. FAILURE TO FOLLOW THESE INSTRUCTIONS

COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN.

6. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly grounded

power supply. Use of an extension cord is not recommended. Electrical circuit should be fused with

slow blow or HACR circuit breaker.

Design Data

Model

Voltage

Hz

Full Load

Amps

Phase

BTU/Hr. @

Max Ambient

Temperature

Max Ambient

Temperature

(°F/°C)

Shipping

Weight

(lb./kg)

T150116GXXX

115

60

3.6

1

800

131/55

27/12.3

T150116GXXX

100

50

3.8

1

800

125/52

27/12.3

T150126GXXX

230

60

1.5

1

900

131/55

27/12.3

T150126GXXX

220

50

1.4

1

800

125/52

27/12.3

Dimensional Drawing

FRONT

3/8 INCH DRAIN STUB

MOUNTING HARDWARE FOR FULLY RECESSED

MOUNTING IS BEHIND REMOVEABLE FRONT COVER.

CLEANABLE, REUSEABLE ALUMINUM INLET FILTER

SLIDES OUT SLOT IN BOTTOM OF FRONT COVER.

RIGHT

TOP

BACK

AMBIENT

AIR OUT

AMBIENT

AIR IN

ENCLOSURE

AIR IN

POWER

CORD

EXIT

FIELD CHANGEABLE POWER

CORD LOCATION (OPPOSITE

SIDE OF UNIT)

1/4-20 MOUNTING HOLES (8)

(4 ON BACK FACE; 4 BEHIND

FRONT COVER)

ENCLOSURE

AIR OUT

*
*
*

*