AMX Incandescent Dimmer Module RDM-INC User Manual

Installation sheet, Rdm-inc incandescent dimmer module 2400 w

Advertising
background image

Installation Sheet

RDM-INC Incandescent Dimmer Module

2400 W

The RDM-INC Incandescent Dimming Module is designed for use with the
RDA series of enclosures, in a AMX Lighting™ modular digital dimming
system. It is a standard 2400 W incandescent dimmer. It can dim incandes-
cent lights, cold-cathode, neon and two-wire dimmable ballasts. The RDM-
INC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL
approved.

RDM-INC UL and C-UL Ratings:

120 VAC, 50/60 Hz, 2400 W

240/277 VAC, 50/60 Hz, 2400 W

Suggested Dimmed Loads:

Incandescent

Low-voltage

Neon, cold-cathode

Two-wire, phase-controlled ballast

Specifications:

Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.985 cm)

Phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 7 in-lbs. (0.8 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 3.7 lbs. (1.67 kg)

BTU/hr: 300

Control current: 45 mA @ 12 VDC

Choke: 350 µS Rise time @ 120 VAC

175 µS Rise time @ 240 VAC

Caution: Pre-Installation Notes:

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

Run all low-voltage and control wires away from heat producing parts

of the dimmer.

Each dimming circuit must have a separate neutral connection.

All electrical ratings are for continuous duty.

AC lighting loads only.

For indoor use only.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-INC to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-INC

350µS
Choke

Line In

Line Out

Low-voltage control
wiring: 4-pin
connector to AMX
Lighting master
controller

20 A power device

High-voltage
connections

Mounting
points

FIG. 2 Connecting the RDM-INC to the AMX Lighting Master

FIG. 3 Sample wiring diagram

Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)

RDM-INC four-pin module connector

4-pin plug from a RDM series module

Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).

2 (-)

1 (+)

Neutral

Load

Neutral

Load

Neon lights
(cold-cathode, on/off)

Two-wire dimmable ballast

All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for each
load.

Load

Line in
(HOT)

Circuit breaker
panel

Advertising