Connection of ranger 9 to premises wiring – Lincoln Electric IM511 RANGER 9 User Manual

Page 23

Advertising
background image

2. Take necessary steps to assure load is

limited to the capacity of the Ranger 9 by
installing a 40 amp, 230 volt double pole
circuit breaker. Maximum rated load for each
leg of the 230 volt auxiliary is 40 amperes.
Loading above 40 amps will reduce output
voltage below the allowable - 10% of rated
voltage which may damage appliances or
other motor-driven equipment.

3. Install a 50 amp 115/230 volt plug (NEMA

Type 14-50) to the Double Pole Circuit
Breaker using No. 8, 4 connector cable of
the desired length. (The 50 amp 115/230 volt
plug is available in the optional plug kit).

4. Plug this cable into the 50 amp 115/230 volt

receptacle on the Ranger 9 case front.

CONNECTION OF RANGER 9 TO PREMISES WIRING

-21 -

230 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

230 VOLT

115 VOLT

115 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 8 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

230 VOLT

GROUNDED CONDUCTOR

40 AMP

230 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 115/230

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 115/230 VOLT

RECEPTACLE