Edwards Signaling ESL 700 SERIES User Manual

Esl 700 series, Installation, Warning

Advertising
background image

1

ESL 700 Series

1

3

2

1

3

2

6

4

5

1

3

2

6

4

5

ESL 700 SERIES

Commercial Self-Diagnostic
Smoke Detectors

Installation Instructions

The ESL 700 Series self-diagnostic detectors provide field-replaceable

optical chambers, and rate-of-rise heat detectors with fast response

algorithms in some models (711UT, 721UT, and 741UT).

Electrical Compatibility

The two-wire units are compatible with a wide range of UL Listed control

panels. For information on detector/control unit compatibility, refer to

ESL’s Compatibility Index. For a copy of the Compatibility Index, call

800-648-7424 or visit the Publication Library at www.ge-security.com.

WARNING !

System may not operate if the detector is not connected

to the control unit initiating device circuit as specified

in the detector or control unit literature.

For optional four-wire operation, compatibility listings with individual

panels are not available from UL, therefore you only need to verify that

the voltage range of the detector equals or exceeds the voltage range of

the control panel power supply, and sufficient current is available to

insure the operation of all detectors.

California State Fire Marshal Approved
MEA (New York City) Approved

700 Series 2-Wire Wiring Diagram

NOTE:

Alarm contacts shown

in non-alarm mode.

Fire Alarm

Initiating Circuit

Compatible Listed

Control Unit

Screw terminal

enlargement detail

Continuity

Switch

Base 701U

for Head Model 711U

Base 702U or 702E
for all Head Models

Base 702RU, 702RE, 702U, or

702E; for Heads Model 731U

First Detector

Last Detector

Remote Test
Switch, N.O.

Remote LED
Blinks every 9 seconds during normal condition
Blinks once every second during trouble condition
Latches on in alarm
No indication during loss of power

Normally Open

Common

Normally Closed

End-of-Line

Device

1

3

2

6

4

5

1

3

2

6

4

5

+

NOTE: Alarm contacts shown
in non-alarm mode.

700 Series 4-Wire Wiring Diagram 741UT Head

Figure 1. Wiring diagrams

Remote LED
Blinks every 9 seconds during normal condition
Blinks once every second during trouble condition
Latches on in alarm
No indication during loss of power

First Detector

Last Detector

Continuity

Switch

Screw terminal

enlargement detail

End-of-Line

Device

Base 702U or 702E

(Relay in Head)

Base 702U or 702E

(Relay in Head)

Power Supervision

Unit (204-12/24V)

Red

Black

Brown

Brown

DC

Power

Circuit

Fire

Alarm

Initiating

Circuit

Installation

Placement and Spacing

Use the following location guidelines to optimize performance and reduce

the chance of false alarms:

• Locate ceiling-mounted smoke detectors in the center of a room or

hallway at least 4 inches (10cm) from any walls or partitions.

Locate wall-mounted smoke detectors so the top of the unit is 4 to 12
inches (10 to 30cm) below the ceiling. See Figure 1.

Locate in a suitable environment as follows:

- Temperature between 32°F (0°C) and 100°F (38°C)

- Humidity between 0 and 95% non-condensing

Locate away from air conditioners, heating registers, and any other
ventilation source that may interfere with smoke entering the unit.

Mount units on a firm permanent surface.

When more than one detector is required, spacing of 30 feet (9.1m)
may be used as a guide on smooth ceilings. Other spacing may be used
depending on ceiling height, high air movement, and other conditions
or response requirements.

Locate away from kitchens, wood stoves, garages, furnaces, and
bathrooms.

Advertising