400 series, En - 47, Protective conductor and the earthing – HT instruments SPEED418 User Manual

Page 48: The previous anomalous results cannot be saved

Advertising
background image

400

Series

EN - 47

9. If the instrument detects an

extremely high earth
resistance, so that it deems
the earth conductor or the
earthing absent, it does not
perform the test and displays
the message reported here
to the side. Check the
efficiency of the protective
conductor and the earthing

R a

----

- - - A

FRQ=50.0Hz
VP-N=231V

VP-Pe=160V

MISSING-PE

Inefficient earthing

50V

UL

10. If the instrument detects that,

in case the test should be
performed, a contact voltage
higher than the set limit
would build up in the system
being tested, it does not
perform the test and displays
the message reported here
to the side. Check the
efficiency of the

R a

----

- - - A

FRQ=50.0Hz
VP-N=231V

VP-Pe=231V

Ut > Ulim

Dangerous contact voltage

50V

UL

protective conductor and the earthing

11. If, after repeated tests, the

instrument has overheated,
the message reported here
to the side is displayed. Wait
for this message to
disappear before performing
other tests

R a

----

- - - A

FRQ=50.0Hz
VP-N=231V

VP-Pe=231V

Hot temperature

Overheated instrument

50V

UL

12.

The previous anomalous results cannot be saved