Caution – HT instruments MACROTEST 5035 User Manual

Page 17

Advertising
background image

MACROTEST

5035

EN - 16

Standard

Brief description

Test voltage

Maximum limit value

CEI 64-8/6

Systems SELV or PELV

Systems up to 500V (Civil installations)

Systems over 500V

250VDC
500VDC

1000VDC

> 0.250M

> 0.500M

> 1.0M

CEI 64-8/4

Floor and wall insulation in civil installations

Floor and wall insulation in systems over 500V

500VDC

1000VDC

> 50k

Ω (if V<500V)

> 100k

Ω (if V>500V)

EN60439

Electrical panel boards 230/400V

500VDC

> 230k

EN60204

Electrical equipment of machines

500VDC

> 1M

Test voltage values and the relative maximum limit values for the most common kinds of test.

CAUTION

If

“Measuring” is displayed the instrument is effecting the measurement.

During this phase do not disconnect the test leads as the circuit under test
may remain charged at a dangerous voltage due to the parasite capacities of
the installation. Independently of the working mode selected the instrument
throws a resistance in the output terminals at the end of each test to
discharge the parasite capacities of the circuit.



4.2.1.1. Mode

"MAN"

6. Press

the

START/STOP key.



The instrument effects the test lasting:

Minimum 6 seconds in case the key is pressed and released within 5 seconds.
Until the key is released for all the other cases.

At the end of the test, in case

the

resistance value R

ISO

detected results

to be lower than R

MAX

(depending on

the selected voltage see following table)
and the test is effected at the
selected rated voltage value
, the
instrument emits a

double sound

signal

indicating the positive

outcome of the test displays one
screen similar to the screen alongside.

R

ISO

1.00

M

500 V 20

s


MAN



The values of measured resistance of isolation always must be confronted with the
normative limits (see table) for being able to assert if the system is to norm.

SAVING:

The test can be stored pressing the

SAVE key twice

(according to paragraph 5.1).


Rated voltage value
selected for the test.

Test duration.
In this case the
START/STOP
key has been
pressed for 20
seconds.

Manual mode.

SAVE

R

ISO

insulation

resistance value

.

START

STOP

Advertising