HT instruments MACROTEST 5035 User Manual

Page 38

Advertising
background image

MACROTEST

5035

EN - 37

If the instrument detects that the earth

cable (green) is not connected, the
screen alongside is displayed for 5
seconds then the initial display is back.
Check the connections of PE conductor
under test.

LOOP

o

>

1999




no

PE

If a contact voltage

U

t

higher than the

selected limit (U

L

) is detected the

instrument

interrupts the test and emits

a long sound signal at the end of the
test and displays the values
alongside.displays the screen
alongside.

LOOP

o

>

50

V

A

UL

t

U

L

=50V

If during the test the instrument detects

a lack of voltage the screen alongside
is displayed.

LOOP

o c

P-P

- - - - - -

t

If the thermistores of the instrument are

damaged, it displays the screen
alongside.

LOOP

o

c

If the instrument gets overheated it

does not permit to effect the tests and
displays the message alongside. Wait
until the instrument displays the initial
screen before proceeding with
measuring.

LOOP

o


THE PREVIOUS RESULTS CANNOT BE SAVED.

Message

“no PE”: the

instrument does
not detect the
protection circuit.

Messagge

“hot”:

the instrument is
overheated.

P-P or P-N
or P-PE

Message

"Att

UL":
a too high
contact voltage
was detected

Message

">50" o “>25V”: the instrument detects

a contact voltage higher than the selected limit
(50V in this case).

The instrument
can display 0° or
180°

SAVE