HT instruments MACROTEST 5035 User Manual

Page 46

Advertising
background image

MACROTEST

5035

EN - 45

If under

P-PE mode the instrument

caries out the test and detects a

global

earth resistance to higher than
1999

Ω, the screen alongside is

displayed for 5 seconds then the initial
display is back.

RCD LOOP

o

>

1999

P-PE



31

V

0

A


SAVING:

The tests can be stored pressing the

SAVE key twice

(according to paragraph 5.1).




4.6. EARTH

ρ: EARTH RESISTANCE AND RESISTIVITY MEASUREMENTS


Turn the

switch on EARTH

ρ position.

Switch on the instrument.


The key

FUNC permits to select one of the following measuring modes

(which can be shown cyclically when pressing the key):

Mode

2P” (the instrument measures earth resistance between 2 points).

Mode

3P” (the instrument measures earth resistance using two auxiliary

earth rods).

Mode

ρ“ (the instrument measures earth resistivity).


The resistance is measured with a 4-cables voltamperometric method, so the value
measured is not depending on the utilized cables. For this reason this method doesn’t
need any cables calibration.

If the cables weren’t long enough, lengthen them or utilize cables longer than the standard
ones. Pay attention to always lengthen each cable separate from each one other.

Message

">1999": the
instrument
detects an earth
resistance higher
than 1999

Ω.

Value of contact voltage

U

t

detected referred to

the carried out value of the RCD current set.
Resolution 1V.