2p 0.93 ω, Caution – HT instruments MACROTEST 5035 User Manual

Page 47

Advertising
background image

MACROTEST

5035

EN - 46

4.6.1. Measurement procedure for "2P" test mode
1. Select "

2P" earth measurement mode by means of the F1 key.

2. Connect the Black, Red, Green and Blue cables to the corresponding input terminals of the

instrument

B1, B2, B3, B4 (see possible connections in the following picture).

3. Connect the black, and green cables to the earth plant and red and blue cables to the

auxiliary rod.

B2

B3

B4

B1

2 points earth resistance measurement


4. Press

the

START/STOP key. The instrument starts the test.


At the end of the test the instrument

displays the values alongside.

EARTH

0.96

2P 0.93 Ω


CAUTION

The display of

“Measuring” means that the instrument is measuring. During

this phase never disconnect test leads.


SAVING:

The tests can be stored pressing the

SAVE key twice

(according to paragraph 5.1).



Note: If

START/STOP key was kept pressed, the instrument takes more consecutive

tests.


5. When a new value is acquired the instrument emits a short sound and calculates the

new average value.



6. Press

DISP key to show how many measurements are in average value

calculation and the measuring mode.


7. Press

CLR key if you want to cancel the medium value of the resistance

and the no. of measurements which are included in the calculation.

START

STOP

Mode “2P”.

Measured
resistance value

Average value of earth resistance calculated over
the number of test displayed.

CLR

DISP

SAVE

Advertising