4.6.3. Measurement procedure for "

ρ" test mode

The earth resistivity is a very useful parameter, its value could help the designer to
correctly size the earth rods in an earth plant.

The measurement is taken according to what prescribed for CEI 64.8, IEC 781, VDE 0413,
EN61557-5

1. Select "

ρ" earth measurement mode by means of the F1 key.

2. Connect the Black, Red, Green and Blue cables to the corresponding input terminals of the

instrument

B1, B2, B3, B4 (see possible connections in the following picture).

3. Connect the cables to the auxiliary rods (see connections in the following picture).

B2

B3

B4

B1

a

a

a

a

Earth resistivity measurement


4.

To select the distance

DIST between the rods. This parameter can take

the following values (expressed in meters):

1, 2, 3, 4, 5, 6, 7, 8, 9, 10.


At the end of the test the instrument

displays the values alongside.

-

ρ

5

m

SE

LE




5.

Press

U

L

and S▲s keys to select the distance value.




6. Press

ESC key to leave this menu confirming the settings.



7. Press

the

START/STOP key. The instrument starts the test.


START

STOP

Distance between the rods set value.