PQA400 - PQA823 - PQA824

EN - 108

This screen (Fig. 178) displays, with graphic and numeric indications, the phase delays
expressed in degrees [°] between voltage V31 and current I3. To correctly evaluate this
diagram, it must be remembered that, under purely resistive loads, the angle between the
Delta voltage and the phase current is +30°.

Fig. 178: Phase 3 vector diagram in three-phase 3-wire system or Aron system

The following keys are active on this page:
 The

F1 key (or the PAG item on the display) advances to the following page of

saved values relative to the total vector diagram.

 The

ESC key (or the smart icon on the display) to exit the function and go back

to the “Recording analysis” page (Fig. 143).

5.5.2.5. Measures
In measure mode, the instrument displays the saved values in TRMS as shown in the
following figures:





In this page, the following symbols are used:
V1N

 Neutral - Phase L1 Voltage

V2N

 Neutral - Phase L2 Voltage

V3N

 Neutral - Phase L3 Voltage

VNPE

 Neutral - Ground Voltage

V12

 Phase L1 - Phase L2 Voltage

V23

 Phase L2 - Phase L3 Voltage

V31

 Phase L3 - Phase L1 Voltage

Inv%

 % value of the Negative sequence unbalance

Omo%

 % value of the Zero sequence unbalance

SEQ

 Phase sequence:

”123” => Correct
”132” => Not correct
”023” => No Voltage on B1
”103” => No Voltage on B2
”120” => No Voltage on B3
”100” => No Voltage on B2 and B3
”020” => No Voltage on B1 and B3
”003” => No Voltage on B1 and B2
Hz

 Frequency

I1

 Current on Phase L1

I2

 Current on Phase L2

I3

 Current on Phase L3

IN

 Neutral Current (not available for PQA400)

Fig. 179: Page 1/5 of numeric values for three-phase 4-wire system