SOLAR300 - SOLAR300N

EN - 103

5.7.1.6. EN50160
This page shows a table containing values complying with standard EN50160.

Fig. 167: EN50160 analysis result


Description of the columns:

Param:

It indicates the percentage of the values which must fall within the limits
set in Limits. Example: Hz 100% means that 100% of the frequency
values recorded must fall within a 1%, -1% range of the nominal
frequency value.

OK:

YES indicates that the analysis has had a positive result, NO indicates
that the analysis has had a negative result.

p%@Lim: Percentage of the measured values which falls within the limits set.
Min:

Minimum measured value.

Max:

Maximum measured value.

Limits: Set

reference

limits.


Within this page, the following keys are active:

 The up and down arrow keys move the cursor along the different quantities

 The right and left arrow keys move the column display to the right or to the left

 The

F1 key (or the PARAM item on the display) accesses the page which shows the

settings made (see Fig. 168)

 The

F2 key (or the GRAPH item on the display) accesses the page which shows the

histogram of the quantities in the table (see Fig. 169)

 The

ESC key (or the smart icon ) exits the function and goes back to the “Recording

Analysis” page (see Fig. 154)


This page contains the global result of the EN50160 analysis, the system connection
condition and the parameters set before recording

Fig. 168: Parameters set for EN50160 analysis