HT instruments SOLAR300N User Manual

Page 137

Advertising
background image

SOLAR300 - SOLAR300N

EN - 135

The following keys are active on this page:

 The

F1 key (or the PAG item on the display) advances to the following page

of saved values.

 The

ESC key (or the smart icon on the display) to exit the function and go

back to the “Recording analysis” page (Fig. 181).



In this page, the following symbols are used:
V1N

Phase L1 - Neutral Voltage.

I1

Phase L1 current.

Patt1

Phase L1 active power.

Preatt1 Phase L1 reactive power.
Papp1

Phase L1 apparent power.

Pf1

Phase L1 power factor.

CosPhi1 Cosine of the phase delay between the

Phase L1 voltage and current
fundamentals.


CosPhi represents the theoretical limit value which
can be reached by the Power factor if all harmonics
are eliminated from the electrical system. For
dimensioning a power factor correction system,
reference is usually made to the CosPhi parameter
value.

Fig. 219: Page 3/5 of numeric values for three-phase 4-wire system

The following keys are active on this page:

 The

F1 key (or the PAG item on the display) advances to the following page

of saved values.

 The

ESC key (or the smart icon on the display) to exit the function and go

back to the “Recording analysis” page (Fig. 181).



In this page, the following symbols are used:
V2N

Phase L2 - Neutral Voltage.

I2

Phase L2 current.

Patt2

Phase L2 active power.

Preatt2 Phase L2 reactive power.
Papp2

Phase L2 apparent power.

Pf2

Phase L2 power factor.

CosPhi2 Cosine of the phase delay between the

Phase L2 voltage and current
fundamentals.


CosPhi represents the theoretical limit value which
can be reached by the Power factor if all harmonics
are eliminated from the electrical system. For
dimensioning a power factor correction system,
reference is usually made to the CosPhi parameter
value.

Fig. 220: Page 4/5 of numeric values for three-phase 4-wire system