SOLAR300 - SOLAR300N

EN - 153

7.4.

TEST OF PV-3 SYSTEM WITH REMOTE UNIT SOLAR-02

CAUTION

 The maximum voltage between inputs D1, D2, A1, A2 and A3 is 1000V / CAT

IV 600V to earth. Do not measure voltages exceeding the limits indicated in
this manual. If these voltage limit values are exceeded, the user may be
exposed to electrical shocks and the instrument could get damaged

 Where possible, disconnect the connecting points of the instrument, before

connecting it, by means of disconnecting switches S1 and S2

Fig. 245: Connecting the instrument to a PV-3 system with SOLAR-02

1. Check and, if necessary, change the basic settings of the instrument relative to PV-3

configuration (see § 5.3.1, 5.3.2 and 5.3.3). Also check that the parameters of the
photovoltaic system considered correspond to the set values. For setting of
pyranometer or reference cell sensitivity please refer to the user manual of SOLAR-02

2. Use the remote unit SOLAR-02 under independent mode to perform a possible preliminary

measurement of irradiance.

CAUTION

BEFORE CONNECT DC CLAMP ON CONDUCTOR

Turn on the clamp, select the correct range and press the ZERO key to the
DC clamp in order to eliminate possible residual magnetizations in the
clamp (values of current up to 0.02A are acceptable). Connect the output
of the clamp to the IDC input of the instrument


3. Connect inputs D1 and D2 to the positive and negative string output pole respectively.

Connect inputs A1, A2 and A3 to the phase conductors, respecting the colors as
shown in Fig. 245

4. Connect the DC current clamp to the positive string output conductor by respecting the

direction of the arrow on the clamp itself as indicated in Fig. 245. Check the status of
internal batteries of the DC clamp after the connection to the installation

5. Connect the AC clamps to the Phase L1, L2, L3 conductors by respecting the

direction of the arrow on the clamps as indicated in Fig. 245. Connect the output of
the clamps to the I1, I2, I3 input of the instrument respectively

6. Supply the electric system considered in case it was temporarily put out of service for

connecting the instrument