7.12. USING THE METER IN A THREE PHASE 4 WIRE SYSTEM

CAUTION

 The maximum voltage between inputs D1, D2, A1, A2 and A3 is 1000V /

CAT IV 600V to earth. Do not measure voltages exceeding the limits
indicated in this manual. If these voltage limit values are exceeded, the
user may be exposed to electrical shocks and the instrument could get
damaged

 If possible, before connecting the meter to the electrical equipment under

test turn the power supply off

Fig. 255: Meter connection in a three phase 4-wire system

1. Check and modify the basic settings of meter if necessary (see § 5.3.1) Set 4WIRE

system option.

2. Connect voltage test leads on Phases L1, L2, L3, Neutral and Ground cables

considering the colours as shown in Fig. 255. Verify the result “123 at display
relative to a correct phase sequence indication
(see § 5.2.1) and perform the
corrections if necessary.

3. Connect the transducer current clamps on Phase L1, L2, L3 and Neutral N cables as

shown in Fig. 255 respecting the clamp’s arrow direction indicating the current standard
sequence from generator to load. On Real Time Values’ section screens always
verify the positive value of Active Power and the power factor relative to each
load which should be normally inductive
before starting a recording. Reverse the
clamp by 180 degrees on cables in case of negative readings.

4. Supply the electrical installation under test in case it was temporarily put out of service

for meter connection. The values of parameters are shown by meter at display in Real
Time Values’ section (see § 5.2).

5. Press SAVE key if a instantaneous sample of display values (Instant) should be saved

(see § 5.7). Use HOLD function to stop the values at display if necessary.

6. Check all settings before start a recording (see § 5.4). Press GO/STOP key to enable

and disable a recording on meter (see § 5.6).