SOLAR300 - SOLAR300N

EN - 182

Energy – Single-phase and Three-phase systems – 50/60Hz

Parameter

[Wh,VArh,VAh]

FS clamp

Range

[Wh,VArh,VAh]

Resolution

[Wh,VArh,VAh]

Accuracy (*)

Active energy

Reactive energy

Apparent energy

FS

 1A

0 – 999.9k

0.1 – 0.001k

(0.7%rdg) @

(Pf=1,Vmis>200V,Imis>10%FS)

(0.7%rdg) @

(Pf=1, Vmis > 200V,

Imis>10A if FS=200A)

(0.7%rdg +3dgt) @ (Pf<1 or

Vmis < 200V or Imis < 10%FS

or Imis <10A if FS=200A)

1A< FS

 10A

0.000 – 99.99k 0.001k – 0.01k

10A< FS < 200A

0.00 – 999.9k

0.01k – 0.1k

200A< FS

 3000A 0.0 – 9.999M

0.1k – 0.01M

(*) For STD clamp ; Vmis = Voltage at which Power is measured

Power Factor (Cos

) – Single phase / Three phase systems

Range

Accuracy (°)

Resolution (°)

0.20

1.00

1.0

 0.6

0.01

Voltage / Current harmonics

Range Accuracy(*)

Resolution

DC

 25

a

(5.0%rdg+5digits)

0.1V / 0.1A

26

a

 33

a

34

a

 49

a

(*) Accuracy to add at correspondent TRMS paramters


Frequency

Range Accuracy

Resolution

42.5

69.0Hz

(0.2%rdg+1dgt)

0.1Hz


Flicker – Single phase / Three phase systems

Parameter Range Accuracy

Resolution

Pst1’, Pst

0.0

10.0

compliance to

EN50160

0.1

Plt

Irradiation measurement (by means of remote unit SOLAR-01 and imput PYRA)

Range Accuracy

Resolution Overcharge

protection

0.00

12.00mV

(1.0%rdg+5dgt)

0.01mV

5V

0.00

 40.00mV

0.02mV

Temperature measurement (by means of remot unit SOLAR-01 and input TEMP with PT1000 probe)

Range Accuracy

Resolution Overcharge

protection

0

 100°C

(1%rdg+2dgt)

1°C 5V