10.5.4. Presence of harmonics: consequences
In general, even harmonics, i.e. the 2

nd

, 4

th

etc., do not cause problems. Triple harmonics,

odd multiples of three, are added on the neutral (instead of deleting each other) thus
creating a condition of overheating of the wire which is extremely dangerous.
Designers should take into consideration the three issues given below when designing a
power distribution system that will contain harmonic current:

 The neutral wire must be of sufficient gauge.

 The distribution transformer must have an additional cooling system to continue

operating at its rated capacity when not suited to the harmonics. This is necessary
because the harmonic current in the neutral wire of the secondary circuit circulates in
the delta-connected primary circuit. This circulating harmonic current heats up the
transformer.

 Phase harmonic currents are reflected on the primary circuit and continue back to the

power source. This can cause distortion of the voltage wave so that any power factor
correction capacitors on the line can be easily overloaded.


The 5

th

and the 11

th

harmonic contrast the current flow through the motors making its

operation harder and shortening their average life.
In general, the higher the ordinal harmonic number , the smaller its energy is and therefore
its impact on the devices (except for transformers).