HT instruments SOLAR300N User Manual

Page 75

Advertising
background image

SOLAR300 - SOLAR300N

EN - 73

5.4.2.10. Inrush current
This option permits to set the control parameters relative to recording of inrush current
events (see § 10.6) which is completely independent from periodic analysis (regulated by
integration period). The below screen is shown by meter:

12/09/2006 – 16:55:10

RECORDING SETTINGS

+ General Parameters
+

Harmonics

Voltage Anom.: 230V 6%-10%

Inrush current: 30A 1s fix

Flicker

Unbalance

132/251 Parameters – Autonomy: 15d 12h

CLP/EXP

PREDEF.

SEL

MODIFY

Fig. 129: Inrush currents selection screen


Press F4 key (alternatively touch MODIFY at display) to set the below parameters for
recording of inrush currents:

The value of current threshold which is correspondent to detection and recording of

inrush current event from meter. This value cannot exceeded the full scale which is
selected for the clamp type used for current measurements (see § 5.3.1.3).

The value of the inrush current detection time interval expressed in seconds. Possible

values which can be set are 1s, 2s, 3s and 4s.

The detection type of inrush currents events. The fix mode (the event is detected

whenever the input current value is over the set threshold) or var mode (the event is
detected if the difference between two instantaneous values in a half period exceed the
set threshold) are possible.

12/09/2006 – 16:55:10

RECORDING SETTINGS

+ General Parameters
+

Harmonics

Voltage Anom.: 230V 6%-10%

Inrush current: 30A 1s fix

Flicker

Unbalance

Inrush current:

30A

1s fix

MOD(+)

MOD(-)

Fig. 130: Inrush current screen - setting control parameters

1. Move the cursor using arrows keys on field relative to “Inrush current” , marked it with

blue background.

2. Use up or down arrow keys or press F3 or F4 keys (alternatively touch the MOD(+) or

MOD(-) s at display) to set the correspondent value. Pressing and holding these keys
permits a rapid values setting, while the single pressure increases or decreases the
value by one single unit. Use left or right arrow keys to move on various fields.

3. Press SAVE or ENTER keys (or the smart icon

) to save each performed setting