HT instruments SOLAR300N User Manual

Page 80

Advertising
background image

SOLAR300 - SOLAR300N

EN - 78

EN50160

MENU GENERAL

PARAMETER

SETTINGS

SYSTEM

Analyzer Settings

System

Not modified

Each system

Freq[Hz]

Clamp Type

FS Clamp[A]

VT Ratio

Analyzer Settings - Advanced

Zoom Graphics

Harm. Type

Harm. Values

Zoom 1st Harm.

Average Values

Recording Settings

Comments EN50160

Each system

Start Not

modified

Stop Not

modified

Integration period

10min

Cogeneration OFF

General Parameters

V1N, Hz

Single phase

V12,V23, V31, Hz

ARON

V1-PE, V2-PE, V3-PE

V12, V23, V31, Hz

3-wire

V1N, V2N, V3N, Average (if

activated), Hz

4-wire

Voltage harmonics

THD, DC, h1, h2, h3…h25

Each system

Current harmonics

OFF

Voltage anomalies

ON

Ref. Voltage anomalies

230V Single,

4-wire

400V 3-wire,

ARON

Up threshold anomalies

+6%

Each system

Low threshold anomalies

-10%

Inrush current

OFF

Flicker

ON

Unbalance

Not available

Single phase

ON 3/4-wire,

ARON

Spike

ON (150V)

Each system

Table 11: Selected parameters of EN50160 configuration