Technical specifications – HT instruments VEGA78 User Manual

Page 113

Advertising
background image

VEGA78

EN - 111

9. TECHNICAL SPECIFICATIONS

9.1. TECHNICAL

FEATURES

TRMS AC/DC Voltage Phase-Neutral / Phase-Ground – Single phase / Three phase systems

Range Accuracy

Resolution

Input

impedance

0.0

 600.0V

(0.5%rdg+2dgt)

0.1V

10M

Max crest factor = 2
Voltage values < 2.0V are considered zero by meter
Meter is connectable with external VT with ratio selectable from 1

 3000

TRMS AC/DC Voltage Phase-Phase – Three phase systems

Range Accuracy

Resolution

Input

impedance

0.0

 1000.0V

(0.5%rdg+2dgt)

0.1V

10M

Max crest factor = 2
Voltage values < 2.0V are considered zero by meter
Meter is connectable with external VT with ratio selectable from 1

 3000

Voltage Anomalies Phase-Neutral – Phase-Phasr Single phase / Three phase 3-wire and 4-wire systems

Range

Voltage

Accuracy

Time Accuracy

(50/60Hz)

Voltage Resolution

Time Resolution

(50/60Hz)

0.0

 600.0V

(1.0%rdg+2dgt)

10ms

0.2V 10ms

0.0

 1000.0V (P-P)

Max crest factor = 2
Voltage values < 2.0V are considered zero by meter
Meter is connectable with external VT with ratio selectable from 1

 3000

Selectable threshold from

1% to 30%

TRMS AC Current with Standard STD transducer clamp

Range Accuracy

Resolution

Input

impedance Overload

protection

0.0

1000.0mV

(0.5%rdg+0.06%FS)

0.1mV

510k

5V

Measure performed with voltage output =1VAC with nominal current measured by clamp
Max crest factor = 3
Current values < 0.1% of full scale (FS) are considered zero by meter

TRMS AC Current with Flex transducer clamp – Range 300A

Range

Accuracy Resolution

Input

impedance Overload

protection

0.0

 49.9A

(0.5%rdg+0.24%FS)

0.1A

510k

5V

50.0

 300.0A

(0.5%rdg+0.06%FS)

Measurements performed with HTFLEX33 flexible clamp
Max crest factor = 3
Current values < 1A are considered zero by meter

TRMS AC Current with Flex transducer clamp – Range 3000A

Range (*)

Accuracy Resolution

Input

impedance Overload

protection

0.0

 3000.0A

(0.5%rdg+0.06%FS)

0.1A

510k

5V

Measurements performed with HTFLEX33 flexible clamp
Max crest factor = 3
Current values < 5A are considered zero by meter

Power – Single phase / Three phase systems (@ Cos

>0.5 and Vmis>60V, clamp type STD)

Parameter

[W, VAr, VA]

Full Scale

Clamp (FS)

Range

[W, VAr, VA]

Accuracy

Resolution

[W, VAr, VA]

Active Power

Reactive Power

Apparent Power

FS

 1A

0.0

 999.9

1.000

 9.999k

(1.0%rdg+6dgt)

0.1

0.001k

1A< FS

 10A

0.000

 9.999k

10.00

 99.99k

0.001k

0.01k

10A< FS

 100A

0.00

 99.99k

100.0

 999.9k

0.01k

0.1k

100A< FS

 3000A

0.0

 999.9k

1.000

 9.999M

0.1k

0.001M

For STD clamp
Vmis = voltage correspondent to power measurement
FS = Full scale clamp

Advertising