KYORITSU 2027 User Manual

Kew snap, Series, Safety warnings

Advertising
background image

Barrier

(2)Press the trigger to open the transformer jaws

and clamp onto a conductor. The most
accurate reading will be obtained by keeping
the conductor at the center of the transformer
jaws.

(3)Read the display.

4-3 AC Voltage Measurement

WARNING

¡

Never use the instrument on a circuit above
600Vrms AC. Measurement on circuits above
this voltage to the instrument or equipment
under test.

¡

Keep your fingers and hands behind the
batteries during measurement.

¡

Do not operate the range switch during a
measurement.

¡

Do not open the battery cover when making
measurement.

(1)Set the range switch to 200V or 600V.
(2)Insert the red plug of the test lead into the V/Ω

terminal and the black plug into the COM
terminal.

(3)Touch the tips of the test leads to the circuit

under test.

(4)Read the display.

4-4 Resistance Measurements and Continuity Check

WARNING

¡

To avoid possible electrical shock and
instrument damage, make sure that a circuit to
be rested is de energized.

¡

Keep your fingers and hands behind the
barrier during measurement.

¡

Do not operate the range switch during a
measurement.

¡

Do not open the battery cover when making
measurement.

(1) Set the range switch to 200Ω.
(2) Insert the red plug of the test lead into the V/Ω

terminal and the black plug into the COM
terminal . With the test leads open, the display
should show “1”on the highest digit(over
range condition)

(3) Short the test leads. The display should read

nearly 0 and the beeper should sound. (Teas
lead have a resistance of about 0.2Ω)

WARNING

¡

Read through and understand the instructions
contained in this manual before starting to use
the instrument.

¡

Save and keep the manual at hand to enable
quick reference whenever necessary.

¡

Be sure to use the instrument only in its
intended applications.

¡

Be sure to understand and follow all safety
instructions contained in the manual.

Be sure to observe the above instructions.
Failure to follow the above instructions may
cause injury, instrument Damage and/or damage
to equipment under test. Kyoritsu is by no means
liable for any damage resulting from the
instrument in contradiction to these cautionary
notes.

○The symbol

indicated on the instrument

means that the user must refer to the related
parts in the manual for safe operation of the
instrument.
Be sure to carefully read the instructions
following each

symbol in the manual.

DANGER is reserved for conditions and

actions that are likely to cause

serious or fatal injury.

WARNING is reserved for conditions and

actions that can cause serious or

fatal injury.

CAUTION is reserved for conditions and

actions that can cause injury or

instrument damage.

○Please refer to following explanation of the

symbols used on the instrument and in this
manual.

User must refer to the explanations in the
instruction manual.
Indicates an instrument with double or
reinforced insulation.
Indicates that this instrument can clamp on
bare conductor when measuring a voltage
corresponding to the applicable Measurement
category, which is marked next to this symbol.
Indicates AC (Alternating Current).

Indicates Earth.

○Read through the following safety instructions

contained in this manual before using the
instrument.

DANGER

¡

Never make measurement on the circuit in which

electrical potential to ground over 600V exists.

¡

Do not attempt to make measurement in the

presence of flammable gasses. Otherwise,

the use of the instrument may cause

sparking, which can lead to an explosion.

¡

Transformer jaw tips are designed not to

short the circuit under test. If equipment

under test has exposed conductive parts,

however, extra precaution should be taken to

minimize the possibility of shorting.

¡

Never attempt to use the instrument if its

surface or your hand is wet

.

Otherwise, you

may get electrical shock.

¡

Never open the Bottom case and Battery

cover during a measurement.

(4)Connect the leads to the circuit to be tested and

read the display.The beeper sounds below
about 30Ω.

4-5 How to Use Data Hold Function
On all ranges, you can hold a reading on the
display using Data Hold function.
(1)While making measurement, press the Data

Hold switch. The last reading remains held on
the display, with a Hold “

”symbol shown

on the display.

(2)Press the Data Hold switch again to exit from

Data Hold function.

WARNING

¡

To avoid electric shock hazard, make sure to
set the range switch to “OFF”and remove
the test leads from the instrument before

try

ng

to replace battery.

If symbol“B”appears on the display, replace the
battery as follows.
(1)Remove test leads from the instrument and set

the range switch to OFF

.

(2)Unscrew and remove the battery compartment

cover.

(3)Replace the battery with a new 9V battery,

Type 1604,PP3, 6F22 or equivalent, observing
correct polarity.

(4)Screw the battery compartment cover.

Model 8004 and 8008 (Multi-Tran) extend the
existing current measuring range and the
maximum conductor size.
(1)Set the range switch to 200A or 600A
(2)Clamp a Multi-Tran on a conductor to be tested.
(3)Clamp KEW SNAP 2017 or 2027 on the pick-

up coil of the Multi-Tran.

(4)Read the display and multiply the reading by

10.

WARNING

¡

Never attempt to make any measurement if the

instrument has any structural abnormality such

as cracked case and exposed metal part.

¡

Do not turn the range switch with rest leads

connected to the instrument.

¡

Do not install substitute parts or make any

modification to the instrument. Return the

instrument to the distributor from whom you

purchased this instrument for repair or re-

calibration.

¡

Always switch off the instrument before

opening the battery compartment cover for

battery replacement.

CAUTION

¡

Always make sure to set the Range switch to

the appropriate position before making

measurement.

¡

Always make sure to insert the plug of each

lead fully into the appropriate terminal on the

instrument.

¡

Be sure to set the Range switch to“OFF”

position after use. When the instrument will not

be in use for a long period, place it in storage

after removing the batteries.

¡

Do not expose the instrument to the direct sun,

high temperature and humidity or dewfall.

¡

Use a damp cloth and detergent for cleaning

the instrument. Do not use abrasives solvents.

○Measurement categories (Over-voltage

categories)

To ensure safe operation of measuring

instruments, IEC61010 establishes safety

standards for various electrical environments,

categorized as CAT I to CAT IV, and called

measurement categories. These are defined as

indicated on the next.

CAT.Ⅰ: Secondary electrical circuits connected to

an AC electrical outlet through a transformer

or similar device.

CAT.Ⅱ: Primary electrical circuits of equipment

connected to an AC electrical outlet by a

power cord.

CAT.Ⅲ: Primary electrical circuits of the equipment

connected directly to the distribution panel,

and feeders from the distribution panel to

outlets.

CAT.Ⅳ: The circuit from the service drop to the

service entrance, and to the power meter and

primary over-current protection device

(distribution panel).

¡

Designed to CAT. Ⅲ 600V and pollution degree

2 specified by the international safety standard,

IEC 61010-1.

¡

Tear-drop-shaped jaws for ease of use in

crowded cable areas and other tight places.

¡

Data Hold function.

¡

Wide frequency range from 40Hz to 1kHz.

¡

KEW SNAP 2027 is a true RMS Type that

permits most accurate measurements

independent of waveforms.

1. Safety Warnings

○This instrument has been designed,

manufactured, and tested according to IEC
61010: Safety requirements for Electronic
measuring apparatus, and delivered in the best
condition after passed the inspection.
This instruction manual contains warnings and
safety rules which must be observed by the user
to ensure safe operation of the instrument and to
retain it in safe condition.
Therefore, read through these operating
instructions before using the instrument.

KEW SNAP

SERIES

KEW SNAP 2017
KEW SNAP 2027

INSTRUCTION MANUAL

DIGTAL AC CLAMP METER

¡

Effect of conductor position :

2017 Within 2% of indicated value at the center

to a 10mm‐dia conductor carrying 100A,

at every part inside the jaws.

2027 Within 3% of indicated value at the center

to a 10mm‐dia conductor carrying 100A,
at every part inside the jaws.

¡

Effect of external : 2 A or less in AC magnetic

field of magnetic field 400A/m

¡

Power Source : 6F22(9V DC) or equivalent

battery

¡

Battery Life : Approx. 200 hours (continuous)

¡

Current consumption : Approx. 2mA

¡

Withstanding Voltage : 5550V AC for 1 minute

between housing case and

metal part of jaws

¡

Insulation Resistance : 50MΩ or greater at

1000V between housing

case and metal part of

jaws

¡

Conductor Size : Approx. 30mm diameter max.

¡

Dimensions : Approx. 91(W)×208(H)×40(D)mm

¡

Weight : Approx. 400g(batteries included)

¡

Safety Standard : EN61010-1

EN61010-031
EN61010-2-032

(600V AC CAT. Ⅲ, Pollution degree2, indoor use)
¡

EMC Standard:EN 55022

¡

Accessories : Test leads Model 7066

……1set

6F22 battery …………………1
Carrying case Model 9079 …1
Instruction Manual

…………1

¡

Optional Accessories : Clamp adapter Model

8004, 8008

4-1 Preparation to check battery voltage;
(1)Set the range switch to a desired position
(2)If the display is clear without symbol “B”

showing, proceed to measurement, Battery
voltage is OK.

(3)If the Display blinks or symbol“B”is indicated,

replace the battery in accordance with Section
5 for Battery Replacement.

4-2 AC Current Measurement

WARNING

¡

Keep your fingers and hands behind the

barrier during measurement.

¡

Do not make measurement with the battery

cover removed from the instrument.

¡

Please be sure to remove a measurement

code before measurement.

(1)Set the range switch to 200A or 600A.

For further information, read the instruction
manual for these models.

¡

Cleaning

Use a cloth dipped in water or neutral detergent

for cleaning the instrument.

Do not use abrasives or solvents, Otherwise,

instrument get damaged, deformed or

discolored.

DISTRIBUTOR

Kyoritsu reserves the rights to change

specifications or designs described in this

manual without notice and without obligations.

4. Operating Instruction

2. Features

¡

Operating System : Dual Integration

¡

Display : Liquid crystal with a max count of 1999

¡

Over rang indication : “1”is displayed on the

highest digit.

¡

Response time : Approx. 2 seconds.

¡

Location for use : Altitude up to 2000m or less,

in-door use

¡

Temperature and Humidity : 23℃±5℃

relative humidity

(Guaranteed Accuracy) 75% or less.

(no condensation)

¡

Operating temperature : ‐10∼50℃,

(no condensation)

up to 30℃,95% relative humidity

up to 40℃,75% relative humidity

up to 50℃,45% relative humidity

¡

Storage temperature and Humidity :

‐20∼60℃, (no condensation)

relative humidity 75% or less

3. Specification

KEW SNAP 2017

Ranges

AC200A

50/60Hz

40Hz∼1kHz

50/60Hz

40Hz∼1kHz

50/60Hz

40Hz∼1kHz

50/60Hz

40Hz∼1kHz

1.5%rdg+4dgt

2.0%rdg+5dgt

1.0%rdg+3dgt

2.0%rdg+5dgt

1.0%rdg+2dgt

1.5%rdg+4dgt

1.0%rdg+2dgt

1.5%rdg+4dgt

sin

AC600A

AC200V

AC600V

200Ω

1.2%rdg+2dgt、Beeps below about 30Ω.

Frequency

Accuracy

Crest Factor

KEW SNAP 2027(True RMS Type)

Ranges

AC200A

50/60Hz

40Hz∼1kHz

50/60Hz

40Hz∼1kHz

50/60Hz

40Hz∼1kHz

50/60Hz

40Hz∼1kHz

1.5%rdg+4dgt

2.0%rdg+5dgt

1.5%rdg+4dgt

2.0%rdg+5dgt

1.0%rdg+2dgt

1.5%rdg+4dgt

1.0%rdg+2dgt

1.5%rdg+4dgt

≦3

sin

≦3

sin

≦3

sin

≦3

sin

AC600A

AC200V

AC600V

200Ω

1.2%rdg+4dgt、Beeps below about 30Ω.

Frequency

Accuracy

Crest Factor

5. Battery Replacement

6. Optional Accessories

7. Maintenance

Model

MODEL8004

Φ 60

Φ100

AC0∼1000A

AC0∼3000A

10:1

10:1

MODEL8008

MAX. Conductor Size. Measuring Range Input to Output Ratio

Over range lndication

Advertising
This manual is related to the following products: